LPC-SVX01C-EN
37
electrical
requirements
Installation
Table ER-3. Motor electrical characteristics & motor/VFD weight, lbs.
utilization
motor
motor
VFD
VFD
hp
voltage
FLA
LRA
RPM
weight
frame size
line input weight
0.5
208/60/1
3.7
17.4
1725
23
56
230/60/1
3.6
17.3
277/60/1
3.2
14.5
1725
23
56
208/60/3
2.1
15
1725
21
56
230/60/3
2.2
13
1725
23
56
460/60/3
1.1
6.5
0.75
208/60/1
5
28.9
1725
33
56
230/60/1
4.9
29
277/60/1
4.2
29
1725
33
56
208/60/3
3.1
20.5
1725
24
56
230/60/3
3
20
1725
27
56
460/60/3
1.5
10
1
208/60/1
5.3
32.9
1725
35
56
230/60/1
5
33
277/60/1
4.1
30
1725
35
56
208/60/3
3.1
20.3
1725
33
56
6.3
27
230/60/3
2.8
20
6.3
27
460/60/3
1.4
10
2.5
27
575/60/3
1.1
8
1725
34
56
2.3
31
400/50/3
2.1
16.8
1450
39
56
2.8
27
1.5
208/60/3
5
34.4
1740
6.3
27
230/60/3
4.6
34
6.3
27
460/60/3
2.3
17
2.5
27
575/60/3
1.65
12.6
1740
39
56
2.3
31
400/50/3
2.5
19.7
1450
40
56
2.8
27
2
208/60/3
5.9
42.3
7.3
27
230/60/3
5.6
42
1725
7.3
27
460/60/3
2.8
21
3.4
27
575/60/3
2.2
16.8
1740
45
56
2.6
31
400/50/3
3.6
31.6
1450
56
56
3.8
27
3
208/60/3
8.7
64.7
10.4
31
230/60/3
8
64
1725
10.4
31
460/60/3
4
32
4.8
27
575/60/3
3.2
25.6
1725
56
56
3.8
31
400/50/3
5.5
44.6
1450
74
182-4T
5.3
27
5
208/60/3
14
91.8
16.8
31
230/60/3
13.2
91
1740
16.8
31
460/60/3
6.6
45.5
8.3
31
575/60/3
5.3
36.4
1740
74
182-4T
5.9
31
400/50/3
9.5
68.1
1450
113
213-5T
9.1
31
7.5
208/60/3
22.2
139.4
23.8
76
230/60/3
21.6
138.8
1760
23.8
76
460/60/3
10.8
69.4
10.6
31
575/60/3
8
49
1760
113
213-5T
9.2
31
400/50/3
13.5
89.5
1450
129
213-5T
15.2
31
10
208/60/3
28
180
32.2
76
230/60/3
28
180
1760
32.2
76
460/60/3
14
90
14.2
31
575/60/3
11
72
1760
131
213-5T
11.1
31
400/50/3
18.5
148.7
1450
167
254T
24.0
76
15
208/60/3
40.6
301
48.3
84
230/60/3
40.6
301
1760
48.3
84
460/60/3
20.3
150.5
21.0
76
575/60/3
16.2
120
1760
162
254T
16.6
76
400/50/3
23
148
1465
235
254-6T
24.0
76
20
208/60/3
61
298
1760
198
254-6T
61.9
84
230/60/3
50
300
1760
235
254-6T
61.9
84
460/60/3
25
150
27.6
76
575/60/3
20
135
1760
242
254-6T
21.4
76
Summary of Contents for LPC
Page 50: ...50 LPC SVX01C EN Operation general information Figure O GI 9 Tracer AH540 termination board ...
Page 91: ...LPC SVX01C EN 91 Maintenance diagnostics Table M D 2 Tracer AH540 541 diagnostics ...
Page 92: ...92 LPC SVX01C EN Maintenance diagnostics Table M D 2 continued Tracer AH540 541 diagnostics ...
Page 94: ...94 LPC SVX01C EN Maintenance troubleshooting Table M T 2 Valves stay open ...
Page 95: ...LPC SVX01C EN 95 Maintenance troubleshooting Table M T 3 Valves stay closed ...
Page 96: ...96 LPC SVX01C EN Maintenance troubleshooting Table M T 4 Outdoor air damper stays open ...
Page 97: ...LPC SVX01C EN 97 Maintenance troubleshooting Table M T 5 Outdoor air damper stays closed ...
Page 107: ...LPC SVX01C EN 107 Maintenance appendix Table M A 6 Hard wired CO2 sensor values ...
Page 109: ......