Installation
Suction Line
Line sizing:
Properly sizing the suction line
is critical for ensuring that the oil returns
to the compressor throughout the system
operating envelope. If provided, use the
suction line size(s) recommended by the
manufacturer of the compressor unit. The
selected tube diameter(s) must maintain
adequate refrigerant velocities at all
operating conditions.
Routing:
To prevent residual or con-
densed refrigerant from “free-flowing”
toward the compressor, install the suction
line so it slopes slightly — 1 inch per 10
feet of run [1 cm per 3 m] — toward the
evaporator. Avoid putting refrigerant
lines underground. Refrigerant condensa-
tion, installation debris inside the line,
service access, and abrasion/corrosion
can quickly impair system reliability.
Insulation:
After operating the system
and testing all fittings and joints to verify
the system is leak-free, insulate the
suction lines to prevent heat gain and
unwanted condensation.
Components:
Installing the suction line
requires field installation of these
components: an access port and possibly
a suction filter. Position them as close to
the compressor as possible.
• Access port:
The access port is used to
determine suction pressure and adjust
the TEV. It should be located near the
external equalizer line connection. This
port is usually a Schraeder valve with a
core.
• Suction filter:
If required by the com-
pressor unit, a replaceable-core suction
filter is installed as close to the compres-
sor unit as possible. Adding manual, ball-
type shutoff valves upstream and
downstream of the filter simplifies
replacement of the filter core.
CAUTION
High Temperatures While Brazing!
Disassemble the thermal expansion
valve before completing the brazing
connections. If necessary, wrap the
valve in a cool wet cloth while brazing.
Failure to protect the valve from high
temperatures may result in damage
to internal components.
Summary of Contents for LPC
Page 50: ...50 LPC SVX01C EN Operation general information Figure O GI 9 Tracer AH540 termination board ...
Page 91: ...LPC SVX01C EN 91 Maintenance diagnostics Table M D 2 Tracer AH540 541 diagnostics ...
Page 92: ...92 LPC SVX01C EN Maintenance diagnostics Table M D 2 continued Tracer AH540 541 diagnostics ...
Page 94: ...94 LPC SVX01C EN Maintenance troubleshooting Table M T 2 Valves stay open ...
Page 95: ...LPC SVX01C EN 95 Maintenance troubleshooting Table M T 3 Valves stay closed ...
Page 96: ...96 LPC SVX01C EN Maintenance troubleshooting Table M T 4 Outdoor air damper stays open ...
Page 97: ...LPC SVX01C EN 97 Maintenance troubleshooting Table M T 5 Outdoor air damper stays closed ...
Page 107: ...LPC SVX01C EN 107 Maintenance appendix Table M A 6 Hard wired CO2 sensor values ...
Page 109: ......