18
LPC-SVX01C-EN
Notes:
All dimensions are in inches.
Damper section ships seperate from main unit.
Linkage between dampers factory installed inside
mixing box on drive side.
Note: This is a flanged
edge to secure section
to either the main unit
or another section.
OPENING
OPENING
(6.1)
(6.1)
Installation
dimensions
& weights
Damper section dimensions & weights, in-lbs.
unit
damper
weights
size
H
L
W
A
B
C
D
qty. - size
SW
DW
3
24.5
21.5
31.2
14.0
16.0
7.6
5.8
2 - 14.0 x 16.0
80
98
6
30.5
24.0
44.2
14.0
29.0
7.6
5.8
2 - 14.0 x 29.0
119
147
8
34.5
27.3
48.2
19.7
26.0
11.1
5.8
2 - 19.7 x 26.0
135
170
10
34.5
25.5
60.2
14.0
46.0
7.1
5.8
2 - 14.0 x 46.0
168
208
12
42.0
27.3
68.2
19.7
37.0
15.6
5.8
2 - 19.7 x 37.0
186
237
14
42.0
27.3
68.2
19.7
44.0
12.1
5.8
2 - 19.7 x 44.0
199
248
17
52.0
29.3
76.2
19.7
53.0
11.6
5.8
2 - 19.7 x 53.0
274
340
21
52.0
34.0
76.2
25.5
53.0
11.6
5.8
2 - 25.7 x 53.0
309
376
25
59.5
35.0
78.2
25.5
58.0
10.1
6.0
2 - 25.7 x 58.0
318
399
30
59.5
35.0
91.2
25.5
68.0
11.6
6.0
2 - 25.7 x 68.0
355
447
Damper Section, in.
Airflow
Notes: 1. SW = Single Wall
2. DW = Double Wall
Summary of Contents for LPC
Page 50: ...50 LPC SVX01C EN Operation general information Figure O GI 9 Tracer AH540 termination board ...
Page 91: ...LPC SVX01C EN 91 Maintenance diagnostics Table M D 2 Tracer AH540 541 diagnostics ...
Page 92: ...92 LPC SVX01C EN Maintenance diagnostics Table M D 2 continued Tracer AH540 541 diagnostics ...
Page 94: ...94 LPC SVX01C EN Maintenance troubleshooting Table M T 2 Valves stay open ...
Page 95: ...LPC SVX01C EN 95 Maintenance troubleshooting Table M T 3 Valves stay closed ...
Page 96: ...96 LPC SVX01C EN Maintenance troubleshooting Table M T 4 Outdoor air damper stays open ...
Page 97: ...LPC SVX01C EN 97 Maintenance troubleshooting Table M T 5 Outdoor air damper stays closed ...
Page 107: ...LPC SVX01C EN 107 Maintenance appendix Table M A 6 Hard wired CO2 sensor values ...
Page 109: ......