8
LPC-SVX01C-EN
Installation
general
information
Table I-GI-1. Packaged Climate Changer General Data
Unit size
3
6
8
10
12
14
17
21
25
30
Unit nominal airflow, cfm
1500
3000
4000
5000
6000
7000
8500
10500
12500
15000
Hydronic & DX coil
coil area, ft
2
2.8
5.6
7.5
9.7
12.4
14.3
16.9
20.6
24.2
28.8
width, in.
17.5
22.5
27.5
27.5
35.0
35.0
45.0
45.0
51.2
51.2
length, in.
23.0
36.0
39.0
51.0
51.0
59.0
54.0
66.0
68.0
81.0
velocity, ft./min.
536.7
533.3
537.1
513.3
484.0
488.1
503.7
509.1
516.5
520.3
dry weight, lbs.
Note
10
1-row
23.5
35.0
41.8
51.5
66.2
72.1
82.8
93.2
109.7
122.5
2-row
29.5
46.3
56.8
70.8
91.0
100.5
116.6
134.2
168.5
190.2
4-row
46.6
75.8
94.7
120.5
152.8
170.7
207.3
240.7
276.3
317.0
6-row
58.6
98.5
124.7
159.3
202.4
227.8
274.9
322.8
372.7
431.2
8-row
73.6
125.4
159.5
204.7
259.4
292.9
351.3
414.5
479.5
556.8
wet weight, lbs.
Note
10
1-row
29.2
43.6
52.5
64.0
85.8
93.2
108.2
121.5
141.9
158.2
2-row
37.7
59.0
73.0
90.5
119.9
132.4
161.1
184.4
226.6
255.4
4-row
59.8
97.6
123.1
155.7
201.6
225.4
279.1
323.9
373.1
427.8
6-row
76.9
129.4
165.2
210.0
271.2
305.3
374.0
438.9
508.2
587.7
8-row
96.9
165.5
212.2
271.0
348.2
393.3
477.6
563.5
653.7
759.0
waterflow limits
1-row
min. gpm
Note
3
6.1
7.9
9.6
9.6
12.2
12.2
15.7
15.7
17.5
17.5
max. gpm
Note
4
32.6
42.0
51.3
51.3
65.3
65.3
83.9
83.9
93.3
93.6
2, 4, 6, & 8-row
min. gpm
Note
3
6.1
14.9
18.4
18.4
23.6
23.6
30.6
30.6
35.0
35.0
max. gpm
Note
4
32.6
79.3
51.3
51.3
65.3
125.9
163.2
163.2
186.6
186.6
volume, gallons
1-row
0.7
1.0
1.3
1.5
2.3
2.5
3.1
3.4
3.9
4.3
2-row
1.0
1.5
2.0
2.4
3.5
3.8
5.3
6.0
7.0
7.8
4-row
1.6
2.6
3.4
4.2
5.9
6.6
8.6
10.0
11.6
13.3
6-row
2.2
3.7
4.9
6.1
8.3
9.3
11.9
13.9
16.3
18.8
8-row
2.8
4.8
6.3
7.9
10.6
12.0
15.2
17.9
20.9
24.3
Steam coil
area, ft
2
1.9
4.5
6.5
8.5
11.7
13.5
6.8
8.4
11.0
13.2
width, in.
Note 5
12.0
18.0
24.0
24.0
33.0
33.0
18.0
18.0
24.0
24.0
length, in.
Note 6
23.0
36.0
39.0
51.0
51.0
59.0
54.0
67.0
66.0
79.0
area, ft
2
Note 7
–
–
–
–
–
–
9.0
11.2
11.0
13.2
width, in.
Notes 5 & 7
–
–
–
–
–
–
24.0
24.0
24.0
24.0
length, in.
Notes 6 & 7
–
–
–
–
–
–
54.0
67.0
66.0
79.0
weight, lbs.
31.7
54.8
74.8
86.0
114.1
123.3
157.6
179.9
200.0
224.2
Fan/motor data
fan wheel size, in.
9x7
12x9
12x12
15x15
18x15
18x18
20x15
20x20
20x18
22x20
max rpm
2000
1500
1700
1400
1200
1200
1100
1000
1300
1150
motor HP
1
/
2
- 2
1
/
2
- 3
3
/
4
- 5
1 - 5
1 - 7
1
/
2
1 - 7
1
/
2
1 -10
2 - 15
3 - 20
3 - 20
min. design cfm
Note
8
1050
2100
2800
3500
4200
4900
5950
7350
8750
10500
max. design cfm
Note 9
1800
3600
4800
6000
7200
8400
10200
12600
15000
18000
2 and 4-in. Flat filter data
quantity - size in.
1 - 20x25
2 - 20x25
2 - 20x25
1 - 16x25
2 - 16x20
2 - 16x20
2 - 16x20
2 - 16x20
2 - 16x25
6 - 16x25
2 - 20x25
1 - 16x25
1 - 16x25
2 - 16x25
2 - 16x25
6 - 20x25
4 - 20x25
2 - 20x20
2 - 20x20
2 - 20x20
2 - 20x20
1 - 20x25
1 - 20x25
2 - 20x25
2 - 20x25
area, ft
2
3.5
6.9
6.9
9.7
16.3
16.3
22.5
22.5
26.4
30.6
nominal air velocity, ft./min.
432.0
432.0
576.0
514.3
369.2
430.8
377.8
466.7
473.5
490.2
2-in. Angle filter section data
quantity - size in.
2 - 16x25
4 - 20x20
4 - 20x20
4 - 20x20
9 - 20x20
9 - 20x20
6 - 16x25
6 - 16x25
4 - 16x20
12 - 16x20
2 - 16x20
6 - 20x25
6 - 20x25
12 - 20x20
8 - 20x20
area, ft
2
5.6
11.1
11.1
15.6
25.0
25.0
37.5
37.5
42.2
48.9
velocity, ft./min.
270.0
270.0
360.0
321.3
240.0
280.0
226.7
280.0
296.2
306.7
Mixing section
nominal air velocity, ft./min.
966.4
1066.3
1123.4
1120.4
1184.1
1161.7
1171.1
1120.1
1218.5
1247.1
Notes:
1. Coil width = length in the direction of a coil header, typically vertical.
2. Coil length = length of coil in direction of the coil tubes, typically horizontal and perpendicular to airflow.
3. Unit sizes 17-30 have two stacked steam coils. 4. To prevent erosion/noise problems. 5.
Coil width = length in the direction of a coil header, typically vertical. 6
. Coil length = length of
coil in direction of the coil tubes, typically horizontal and perpendicular to airflow. 7.
The minimum waterflow is to assure self venting of the coil. There is no minimum water flow limit
for coils that do not require self venting. 8.
Minimum airflow limit is for units with hot water, steam, or electric heat. There is no minimum airflow for cooling only units. 9. Due to
moisture carryover limits. 10. Coil weight based on 12 fpi coil.
Summary of Contents for LPC
Page 50: ...50 LPC SVX01C EN Operation general information Figure O GI 9 Tracer AH540 termination board ...
Page 91: ...LPC SVX01C EN 91 Maintenance diagnostics Table M D 2 Tracer AH540 541 diagnostics ...
Page 92: ...92 LPC SVX01C EN Maintenance diagnostics Table M D 2 continued Tracer AH540 541 diagnostics ...
Page 94: ...94 LPC SVX01C EN Maintenance troubleshooting Table M T 2 Valves stay open ...
Page 95: ...LPC SVX01C EN 95 Maintenance troubleshooting Table M T 3 Valves stay closed ...
Page 96: ...96 LPC SVX01C EN Maintenance troubleshooting Table M T 4 Outdoor air damper stays open ...
Page 97: ...LPC SVX01C EN 97 Maintenance troubleshooting Table M T 5 Outdoor air damper stays closed ...
Page 107: ...LPC SVX01C EN 107 Maintenance appendix Table M A 6 Hard wired CO2 sensor values ...
Page 109: ......