Operation
general
information
Figure O-GI-10. Power requirements
Operator display
This section explains how to install a
Tracer AH540/541 operator display and
set up the operator display.
Installing the stand-alone operator
display
With the attached cable, the stand-alone
operator display (see Figure O-GI-11)
can be mounted up to 10 ft (3 m) from the
Tracer AH541 controller. You can extend
this distance up to 150 ft (46 m) using
four-conductor wire and the included pig-
tail connectors. Alternately, use three
twisted-pair wires. Trane recommends
the following four-conductor wires:
•
Plenum 18 AWG, Trane part number
400-2059
•
Plenum 22 AWG, Trane part number
400-2020
•
Non-plenum, Trane part number 400-
1005
Figure O-GI-11. Tracer AH541 stand-alone
operator display
CAUTION
Avoid
Equipment Damage!
To
clean the operator display, use a cloth
dampened with commercial liquid
glass cleaner. Spraying water or
cleansers directly on the screen may
result in equipment damage.
Termination board
Main controller board
Transformer
Line
voltage
24 Vac
Summary of Contents for LPC
Page 50: ...50 LPC SVX01C EN Operation general information Figure O GI 9 Tracer AH540 termination board ...
Page 91: ...LPC SVX01C EN 91 Maintenance diagnostics Table M D 2 Tracer AH540 541 diagnostics ...
Page 92: ...92 LPC SVX01C EN Maintenance diagnostics Table M D 2 continued Tracer AH540 541 diagnostics ...
Page 94: ...94 LPC SVX01C EN Maintenance troubleshooting Table M T 2 Valves stay open ...
Page 95: ...LPC SVX01C EN 95 Maintenance troubleshooting Table M T 3 Valves stay closed ...
Page 96: ...96 LPC SVX01C EN Maintenance troubleshooting Table M T 4 Outdoor air damper stays open ...
Page 97: ...LPC SVX01C EN 97 Maintenance troubleshooting Table M T 5 Outdoor air damper stays closed ...
Page 107: ...LPC SVX01C EN 107 Maintenance appendix Table M A 6 Hard wired CO2 sensor values ...
Page 109: ......