Installation - Controls
50
UNT-SVX041D-EN
Note:
Range values are estimated transmission distances
for satisfactory operation. Actual distance is job
specific and must be determined during site
evaluation. Placement of WCI is critical to proper
system operation. In most general office space
installations, distance is not the limiting factor for
proper signal quality. Signal quality is affected by
walls, barriers, and general clutter. For more
information, see os available at www.trane.com.
Output power: North America: 100 mW
Radio frequency: 2.4 GHz (IEEE Std 802.15.4-2003
compliant) (2405–2480 MHz, 5 MHz spacing)
Radio channels: 16
Address range: Group 0–8, Network 1–9
Mounting
Fits a standard 2 x 4-inch junction box (vertical mount
only). Mounting holes are spaced 3.2-inch (83 mm) apart
on vertical center line. Includes mounting screws for
junction box or wall anchors for sheet-rock walls. Overall
dimensions: 2.9 inch (74 mm) by 4.7 inch (119 mm).
Wireless protocol
ZigBee PRO—ZigBee Building Automation Profile, ANSI/
ASHRAE Standard 135-2008 Addendum q (BACnet
®
/
ZigBee)
Installation - Zone Sensors
Zone Sensor Options
Control sensor options include both unit-mounted
(factory-installed) and wall-mounted sensors. Tracer
®
controller options available for the zone sensors are:
•
Tracer® UC400-B delivers single zone VAV control in a
stand-alone operation or as part of a building
automation system using BACnet
®
communications.
Zone sensors have an internal thermistor and operate on
24 Vac. Options with setpoint knobs are available in
Fahrenheit or Celsius. See
through
available options and model number references.
UC400-B Controller Options
Figure 37.
Wall-mounted temperature sensor (SP, OALMH,
OCC/UNOCC)
Figure 38.
Wall-mounted display temperature sensor
(SP, OCC/UNOCC, OALMH, COMM)
Figure 39.
Wall-mounted temperature (OCC/UNOCC,
COMM)
Figure 40.
Wall-mounted temperature sensor (SP,
OCC/UNOCC, OALMH, COMM)