ECM Overview and Setup
UNT-SVX041D-EN
37
Configuration Examples
Example 1
To view the value of parameters without saving. In this
case we wish to verify that the “Low Speed Value” for
Motor 1 is set correctly to 800 rpm.
We start with the motor control board scrolling status
display and proceed as follows:
Example 2
We wish to change the change the value of Low Speed to
820 rpm:
We will continue from the previous example as shown
below, using a long press to “save” the new desired value.
If the display has timed out and returned to the status loop,
repeat Example 1 to arrive back at this example’s starting
point.
Table 22. Button actuation levels
Button
Menu/Set
Duration
Action
Short Press in
Status Display
<1 sec
None
Short Press in Configuration Display
Toggles between parameter name and value without saving
(abandons value if changed).
Long Press/Hold
in Status Display
>3 sec
Enters the configuration menu
Long Press/Hold
in Configuration Display
>3 sec
If on a parameter name, toggles to the value. If on a parameter value,
saves the value settings and returns to the parameter name as
confirmation.
Button
Decrement
Duration
Action
Short Press in
Status Display
<1 sec
None
Short Press in Configuration Display
<1 sec
Scrolls through parameter names, or decreases value of parameter.
Long Press/Hold
in Status Display
>3 sec
n/a
Long Press/Hold
in Configuration Display
>3 sec
Faster scroll through parameter name, or faster decrease of values of
parameters.
Button
Increment
Duration
Action
Short Press in
Status Display
<1 sec
None
Short Press in Configuration Display
<1 sec
Scrolls through parameter names, or increases value of parameter.
Long Press/Hold
in Status Display
>3 sec
n/a
Long Press/Hold
in Configuration Display
Faster scroll through parameter name, or faster increase of values of
parameters.
Figure 24.
Verify low speed value