- 16 -
tousek
/ EN_PULL-TSA_03 / 25. 03. 2020
Important
•
select the setting according to the carried contact strips connections!
•
During the learning phase of the motor the contact edges shouldn´t be triggered, since this would lead to an
error message - the end stops have to be set accordingly.
Important
•
The motor stops when max. set force is exceeded.
•
WARNING: The safety regulations about the force settings must be observed!
Safety edges
Connections and adjustments
P4
Main safety edge
(terminal 50/52),
side safety edge
(terminal 50/51)
0
not active :
the safety devices “closing edges” are not evaluated.
1
only main edge:
main safety edge gets evaluated.
2
only side edge:
side safety edge gets evaluated.
3
MSE and SSE:
main and side safety edge get evaluated.
Safety sensing edges (main and side edge)
•
OBSTACLE DETECTION:
when a contact strip/safety edge is triggered/activated
then a change of direction is effected for 1 second.
After that the gate stops.
i.e.: Hence if the safety edges have to react to obstacles during the closing movement, they have to be serially
connected to the terminals of the main safety edge
If the safety edges have to react to obstacles during the opening movement, they have to be serially connected
to the terminals of the side safety edge
Example: W
8,2kΩ final resistance
1
final edge
2+3
passage edge
S
to control board
If you connect only one safety edge please use a final edge (1).
Side safety edge
Function: safety during
opening movement
Main safety edge
Function: safety during
closing movement
1
W
2
3
S
50
52
50
51
mai
n
safety
ed
g
e
side
s
afety edge
Main safety edge
Side safety edge
52
51
50
8.k2
8.k2
Max. force
Connections and adjustments
P5
factory settings:
7
0
–
9
0–9 adjustable:
defines the max. permissible motor force
(0 =min., 9 = max.)