When the address is set, the wired controller can be removed and connect the centralized controller
to the indoor mainboard. Then connect the required units to realize centralized control of these units.
NOTE
:
(1) When centralized controller is to be connected, set the address mode into centralized controller
address mode through wired controller. Long-distance control address mode can not be set.
(2) The unit addresses in the same network must be different, otherwise, communication malfunction
will occur and the unit can not work normally.
(3) When centralized controller is to be connected, the unit address range is 1-16. Only 16 sets of unit
in maximum can be connected.
(4) The code and model of wired controller is as below:
Name
Product Code
Remark
Centralized controller CE50-24/E
MC207025
Only 16 sets of unit in maximum can be connected to this
controller
7.2.5 Light Board Control
Light board interface is reserved on the mainboard of duct type unit. You can purchase Gree light
board to realize control of the unit. When wired control is also connected, you can realize control of the
unit through light board and wired controller.
Light board information:
Name
Product code
Remark
Receiving board Z6L
Only for duct type unit
There are two buttons on the light board to control ON/OFF of cooling and heating. There are also
other indicators and nixie tube display.