TOSOT DC INVERTER U-MATCH AIR
42
3. Setting method:
(1) Firstly, set the address mode of wired controller into centralized controller address mode. The
setting method is:
Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the
debugging menu. P
ress Mode button to adjust to “10” in temperature displaying zone. Timer zone
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
1) Centralized controller address mode (LCD displays 00).
2) Long-distance control address mode (LCD displays 01).
Choose the second selection and then press Enter/Cancel button to save and exit setting. Now, the
address of wired controller is set to match the address of long-distance control. The unit will memorize
this setting status. The setting value will be memorized after power failure. The detailed setting is as
shown in the Figure below:
Figure 2-7-10
(2) Address setting of each unit: when the address mode is set to be long-distance control address
mode. The address setting value range is 01~255. The setting method is:
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting
interface of wired controller address. LCD displays address sequence. Press ▲ or ▼ button to adjust the
address sequence and then press Enter/Cancel button to confirm. The setting value will be memorized
after power failure. The detailed setting is as shown in the Figure below: