TOSOT DC INVERTER U-MATCH AIR
10
NOTES:
a. The design of this unit conforms to the requirements of ARI 210/240-2008 standard.
b. The air volume is measured at the relevant standard external static pressure.
c. Cooling (heating) capacity stated above is measured under nominal working conditions
corresponding to standard external static pressure. The parameters are subject to change with the
improvement of products, in which case the values on nameplate shall prevail.
—
Indoor
Outdoor
Cooling
DB: 26.7
℃
(80.0
℉
)
WB: 19.4
℃
(67.0
℉
)
DB: 35.0
℃
(95.0
℉
)
WB: 23.9
℃
(75.0
℉
)
Heating
DB: 21.1
℃
(70.0
℉
)
WB: 15.6
℃
(60.0
℉
)
DB: 8.33
℃
(47.0
℉
)
WB: 6.11
℃
(43.0
℉
)
Piping Length
18k~48k units
7.6m(25.0ft)
3.2 Operation Range
Mode
Range of Outdoor Temperature
℃
(
℉
)
Cooling
-18.0(0.0) ~ 46.1(115.0)
Heating
-18.0(0.0) ~23.9(75.0)
3.3 Electrical Data
3.3.1 Outdoor unit
Table 1-4-1 Electrical Data of Outdoor Unit
Model
Compressor
Fan Motor
Fuse/Breaker
Capacity
Minimum
Circuit
Ampacity
Power Supply
Qty.
RLA
FLA
V/Ph/Hz
—
A
A
A
A
TUHD18ND3F1O
208V/230V ~ 60Hz
1
11.0
0.7
5/25
15.3
TUHD24ND3F1O
208V/230V ~ 60Hz
1
17.5
0.6
5/35
23.4
TUHD30ND3F1O
208V/230V ~ 60Hz
1
17.5
0.6
5/35
23.4
TUHD36ND3F1O
208V/230V ~ 60Hz
1
22.0
2.0
5/50
29.5
TUHD42ND3F1O
208V/230V ~ 60Hz
1
22.0
2.0
5/50
31.5
TUHD48ND3F1O
208V/230V ~ 60Hz
1
22.0
2.0
5/50
32.5