TOSOT DC INVERTER U-MATCH AIR
44
3. Setting method:
Firstly, set the address mode of wired controller into centralized controller address mode. The
setting method is:
(1) Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the
debugging menu. Press Mode button
to adjust to “10” in temperature displaying zone. Timer zone
displays setting state and
press ▲ or ▼ button to adjust. There are 2 selections:
1) Centralized controller address mode (LCD displays 00).
2) Long-distance control address mode (LCD displays 01).
Choose the first selection and then press Enter/Cancel button to save and exit setting. Now, the
address of wired controller is set to match the address of centralized controller. The unit will memorize
this setting status. The setting value will be memorized after power failure. The detailed setting is as
shown in the Figure below:
Figure 2-7-12
(2) Address setting of each unit: when the address mode is set to be centralized controller address
mode. The address setting value range is 01~16. The setting method is:
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting
interface of wired controller address. LCD displays address sequence. Press ▲ or ▼ button to adjust the
address sequence and then press Enter/Cancel button to confirm. The setting value will be memorized
after power failure. The detailed setting is as shown in the Figure below: