Various settings confirmation method
Whether the various settings are in effect or not can be confirmed.
1) Ensure the LED display shows the initial status. If not then ensure to restore the initial status.
2) Push SW01 for at least 5 seconds. D804 will start slowly flashing.
3) Push SW01 several times until reaching the desired function on the LED display. If the setting is valid D804 and
D805 will rapidly flash. (If the setting is invalid then D804 will rapidly flash but D805 will turn off.)
4) Push and hold down SW01 and SW02 at the same time for at least 5 seconds to return the LED display to
the initial state.
Returning to the factory default settings
The factory default settings can be restored using the following procedure.
1) Ensure the LED display shows the initial state. If not then ensure to return it to the initial state.
Return to default factory setting LED display
D800 D801 D802 D803 D804 D805
: Go ON : Go OFF : Flash (5 times/sec)
Sub-P.C. board switch and LED arrangement diagram
D800
(LED YEL)
D801
(LED YEL)
D802
(LED YEL)
D803
(LED YEL)
D804
(LED YEL)
D805
(LED GRN)
SW01
SW02
2) Push and hold down SW01 for at least 5 seconds and
confirm that D804 is slowly flashing.
3) Push SW01 several times until reaching the LED display
(D800 to D805) shown on the right or ‘Returning to the
default factory setting LED display’.
4) Push and hold down SW02 for at least 5 seconds and
confirm that D804 is slowly flashing.
5) Push and hold down SW01 and SW02 at the same time
for at least 5 seconds to return to the initial state LED
display.