– 69 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[L29]
[Communication trouble MCUs]
Is the communication line between
the compressor IPDU P.C. board
(CN 852) and the fan motor IPDU P.C.
board (CN 504) connected?
NO
Correct wiring
NO
Correct wiring
YES
Is the communication line between
the Interface P.C.board (CN 802) and
the fan motor IPDU P.C.board
(CN 505) connected?
YES
Replace compressor IPDU P.C. board.
* When replacing Compressor IPDU P.C.board,
replace the fuse.
[L10]
[Unset model type] Only when service P.C. board is used.
Cut jumper line according
to the explanation sheet packaged
with the service P.C. board.
[P03]
[Discharge temp. trouble]
Is there gas leak?
Is there refrigerant shortage?
NO
Replace the PMV.
Replace TD sensor.
YES
Remove and improve
the cause of overload.
NO
Replace Interface
P.C. board.
NO
Trouble part repair.
Recharge refrigerant.
Is connection of CN603 correct?
Is resistance value of TD sensor correct?
YES
NO
Is PMV normal?
YES
YES
Does an abnormal overload happen?