– 26 –
Systematic diagram of refrigerating cycle
RAV-GM224 series
Pressure
Pipe surface temperature
Compressor
drive revolution
frequency (rps)
Indoor
fan
Indoor/outdoor
temp.condition
(Mpa)
(kg/cm
2
g) Discharge Suction
Indoor heat
exchanger
Outdoor heat
exchanger
Pd
Ps
Pd
Ps
(TS)
(TD)
(TC)
(TL)
(TE)
Indoor Outdoor
2.3
3.8
2.2
2.4
3.3
1.7
1.2
1.4
0.7
0.8
1.2
0.2
Cooling
Heating
Standard
Overload
Low load
Standard
Overload
Low load
23.5
38.7
22.6
24.5
33.7
17.3
12.2
14.3
6.6
8.2
12.2
2.0
91.3
90.8
52.6
90.8
91.3
85.7
14.5
16.3
8.7
2.9
18.6
-28.0
12.0
17.0
1.0
40.0
52.0
29.0
48.4
56.1
39.3
5.9
19.0
-14.3
37.0
55.8
13.9
1.2
17.1
-26.9
48.0
39.0
31.2
56.4
31.2
88.0
HIGH
HIGH
LOW
HIGH
LOW
HIGH
27/19
32/24
18/15.5
20/-
30/-
15/-
35/-
46/-
-15/-
7/6
24/18
-27/-
Pressure
Pipe surface temperature
Compressor
drive revolution
frequency (rps)
Indoor
fan
Indoor/outdoor
temp.condition
(Mpa)
(kg/cm
2
g) Discharge Suction
Indoor heat
exchanger
Outdoor heat
exchanger
Pd
Ps
Pd
Ps
(TS)
(TD)
(TC)
(TL)
(TE)
Indoor Outdoor
2.4
3.8
2.2
2.6
3.3
1.8
1.1
1.4
0.7
0.8
1.2
0.2
Cooling
Heating
Standard
Overload
Low load
Standard
Overload
Low load
24.5
38.7
22.6
26.5
33.7
18.4
11.2
14.3
6.6
8.2
12.2
2.0
95.7
90.8
52.6
98.5
91.3
89.7
12.2
16.3
8.7
3.0
18.6
-28.9
10.0
17.0
1.0
43.0
52.0
30.0
49.5
56.1
39.3
5.9
19.0
-14.3
37.6
55.8
13.9
1.5
17.1
-27.5
59.4
39.0
31.2
66.6
31.2
105.0
HIGH
HIGH
LOW
HIGH
LOW
HIGH
27/19
32/24
18/15.5
20/-
30/-
15/-
35/-
46/-
-15/-
7/6
24/18
-27/-
∗
This compressor has a 4-pole motor.
The value of the compressor frequency (Hz) when measured by a clamp meter is twice the compressor
revolution number (rps).
∗
This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe
length. Data will change depending on the mounted pipe length or combination with the indoor unit.
RAV-GM280 series
∗
This compressor has a 4-pole motor.
The value of the compressor frequency (Hz) when measured by a clamp meter is twice the compressor
revolution number (rps).
∗
This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe
length. Data will change depending on the mounted pipe length or combination with the indoor unit.