– 44 –
Time
correction
+ 1 zone
± 0
–1 zone
(min 1)
Fan speed
(rpm)
L (W6)
L– (W5)
UL (W4)
SUL (W3)
Compressor speed
(rps)
Zone
12
11
10
9
8
7
6
5
4
3
2
1
0
10
31
27
24
20
17
14
11
OFF
13
31
27
24
20
17
14
11
OFF
16
31
27
24
20
17
14
11
OFF
[˚C]
+4.0
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
0
–0.5
–1.0
–3.0
(Room temp.
–
Set temp.)
Ta–Tsc
30 minutes
A
B
C
A
B
C
®
Time Compressor
speed
0 rps
A zone
16 rps
B zone
16 to 52 rps
C zone
52 rps
0
–0.5
–1.0
–1.5
–2.0
–2.5
–3.0
–4.0
–5.0
–6.0
–7.0
–8.0
–9.0
–10.0
–11.0
(Room temp.
–
Set temp.)
Ta–Tsc
Item
10. SLEEP
MODE
operation
Operation flow and applicable data, etc.
When pushing [SLEEP MODE] button on the remote controller, a
quiet and mild operation is performed by reducing the fan speed
and the compressor speed.
<Cooling operation>
This function operates the air conditioner with the difference
between the set and the room temperature (Tsc and Ta) as
shown in the following figure.
The time correction is performed for 8 minutes each.
<Heating operation>
Description
<Cooling operation>
1) The indoor fan speed is con-
trolled between L and SUL.
The compressor speed in control
as shown in the left figure.
2) The set temperature increased
0.5°C per hour up to 2°C starting
from the set temperature when
SLEEP MODE has been
received.
<Heating operation>
1) The indoor fan speed is con-
trolled within (W7) as maximum
value.
2) Setting the compressor speed to
Max. 52 rps, the temperature
zone in which the operation can
be performed with Max. 16 rps is
gradually widened after 30
minutes passed when starting
SLEEP MODE operation.
3) The louver position is set
horizontally (Standard cooling
position)
• When the room temperature
comes close to the Set
temperature.
Or
• When 25 minutes passed after
starting SLEEP MODE
operation.