– 26 –
RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E / RAS-3M18SACV-E
NOTE :
• The maximum pipe length of this air conditioner is 50 m. The additional chaging of refrigerant is unneces-
sary because this air cinditioner is designed with charge-less specification.
• Never connect one indoor unit only. Two or more indoor units should be connected.
Connecting pipe
Thickness : 0.8 mm
9.52 :
RAS-M10SKCVP-E
RAS-M13SKCVP-E
12.7 :
RAS-M16SKCVP-E
NOTE :
Gas leak check position
Refrigerant flow
INDOOR UNIT A
T1
Temp. measurement
To
C room
To
B room
Indoor heat
exchanger
Cross flow fan
Sectional shape
of heat insulator
To
C room
To
B room
Allowable height
difference : 10m
Allowable pipe length
Per 1 unit
Max. : 20m
Min. : 2m
Total
Max. : 50m
P
Strainer
Pulse motor valve
at liquid side
(UKV-18D64)
TGa
TGb
TGc
TD
Accumulating tank
54 370
Compressor
DA130A1F-25F
T
2
Outdoor heat
exchanger
Temp. measurement
Propeller fan
Refrigerant amount : 1.5kg (R410A)
OUTDOOR UNIT
Connecting pipe
Thickness : 0.8 mm
6.35
Pressure
measurement
Gauge attaching port
Vacuum pump
connecting port
( 9.52)
( 9.52)
( 9.52)
( 6.35)
( 6.35)
( 6.35)
TO
Summary of Contents for RAS-3M18SACV-E
Page 21: ... 21 4 2 Outdoor Unit RAS 3M18SAV E RAS 3M18SACV E ...
Page 110: ... 110 MCC 1438 ...
Page 111: ... 111 MCC 818 ...