– 25 –
7. REFRIGERANT CYCLE DIAGRAM
7-1. Indoor Unit, Outdoor Unit
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E / RAS-3M18SAV-E
NOTE :
• The maximum pipe length of this air conditioner is 50 m. The additional chaging of refrigerant is unneces-
sary because this air cinditioner is designed with charge-less specification.
• Never connect one indoor unit only. Two or more indoor units should be connected.
Connecting pipe
Thickness : 0.8 mm
9.52 :
RAS-B10SKVP-E
RAS-B13SKVP-E
12.7 :
RAS-B16SKVP-E
INDOOR UNIT A
T1
Temp. measurement
To
C room
To
B room
Indoor heat
exchanger
Cross flow fan
Sectional shape
of heat insulator
To
C room
To
B room
Allowable height
difference : 10m
Allowable pipe length
Per 1 unit
Max. : 20m
Min. : 2m
Total
Max. : 50m
P
Strainer
Pulse motor valve
at liquid side
(UKV-18D64)
TGa
TGb
TGc
TD
Accumulating tank
54 370
Compressor
DA130A1F-25F
T
2
Outdoor heat
exchanger
Temp. measurement
Propeller fan
Refrigerant amount : 1.5kg (R410A)
OUTDOOR UNIT
Connecting pipe
Thickness : 0.8 mm
6.35
Pressure
measurement
Gauge attaching port
Vacuum pump
connecting port
( 9.52)
( 9.52)
( 9.52)
( 6.35)
( 6.35)
( 6.35)
TO
NOTE : Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
TE