– 102 –
12-3. Outdoor Unit
Upper cabinet
Upper cabinet
Water-proof
cover
Wiring cover
Valve cover
No.
1
Part name
Common
procedure
Procedure
1. Detachment
NOTE
Wear gloves for this job.
Otherwise, you may injure your hands on
the parts, etc.
1) Stop operation of the air conditioner, and
turn off the main switch of the breaker for
air conditioner.
2) Remove the valve cover.
(ST1TØ4 × 8L 1 pc.)
• After removing screw, remove the valve
cover pulling it downward.
3) Remove wiring cover (ST1TØ4 × 8L
2 pcs.), and then remove connecting cable.
4) Remove the upper cabinet.
(ST1TØ4 × 8L 2 pcs.)
• After removing screws, remove the upper
cabinet pulling it upward.
2. Attachment
1) Attach the water-proof cover.
NOTE
The water-proof cover must be attached
without fail in order to prevent rain water,
etc. from entering inside the indoor unit.
2) Attach the upper cabinet.
(ST1TØ4 × 8L 2 pcs.)
• Hook the rear side of the upper cabinet to
claw of the rear cabinet, and then put it on
the front cabinet.
3) Perform cabling of connecting cable, and
attach the wiring cover.
(ST1TØ4 × 8L 2 pcs.)
• Place the wiring cover over the opening
used to work on the connecting wires of
the rear cabinet, and secure it using the
two fixing screws (ST1TØ4 × 8L 2 pcs.).
At this point, the top cushion of the wiring
cover must be on the inside of the open-
ing.
4) Attach the valve cover.
(ST1TØ4 × 8L 1 pc.)
• Insert the upper part into the square hole
of the rear cabinet, set hook claws of the
valve cover to square holes (at three
positions) of the main unit, and attach it
pushing upward.
Remarks