6F3B0250
Basic Hardware and Function
47
2. Specifications
Functional specifications (cont’d)
Item
T1-16
T1-28
T1-40
T1-40S
Real-time clock
/calendar
No
Yes,
(
±
30 s/month)
Special I/O functions
(Note)
High speed counter (2 single or 1 quadrature),
Interrupt input (2 points),
Adjustable analog register (2 points),
Pulse output (CW+CCW or pulse+direction),
PWM output
Communications
interface
1 port RS-232C (programmer port)
- for Programmer or Computer link connection
-
1 port RS-485
- Programmer
- Computer link
- Data link
- Free ASCII
-
TOSLINE-F10 remote
(by option card)
Debug support
function
Sampling trace
(8 devices - 256 times or 1 register - 128 times)
Sampling trace
(8 devices and
3 register - 256
times)
-
On-line
programming
-
On-line
EEPROM write
NOTE
(1) The input specification of the T1-16 (AC power type) is dry contact input,
which supplies the power for input signals (24 Vdc) from the unit.
Other types are DC input, which requires external power for input signals.
(2) High speed counter, interrupt input, pulse output and PWM output are
available in the DC input types.
(3) High speed counter and interrupt input cannot be used simultaneously.
(4) Pulse output and PWM output cannot be used simultaneously.