6F3B0250
Basic Hardware and Function
155
7. Instructions
FUN 019
DMOV
Double-word data transfer
Expression
Input
-
[
A+1
×
A
MOV
B+1
×
B
]
-
Output
Function
When the input is ON, the double-word (32-bit) data of
A+1
×
A is stored in double-word register B+1
×
B.
The data range is -2147483648 to 2147483647.
Execution condition
Input
Operation
Output
OFF
No execution
OFF
ON
Execution
ON
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW
T
C
D
I
J
K
A
Source
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
B
Destination
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Example
When R011 is ON, a double-word data of D0101
×
D0100 is stored in RW17
×
RW16 and the output
is turned ON. If D0101
×
D0100 is 1234567, the data 1234567 is stored in RW17
×
RW16.