6F3B0250
232
T1/T1S User’s Manual
7. Instructions
FUN 146
STOT
Step sequence output
Expression
Input
-
[ STOT
A
]
-ê
Function
When the input is ON, the device
A is set to ON and the devices of STIN instructions on the same rung
are reset to OFF.
Execution condition
Input
Operation
Output
OFF
No execution
-
ON
Execution
-
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW
T
C
D
I
J
K
A
Step device
Ö
Example
See example on STIN (FUN 145) instruction.
Note
·
The STIZ, STIN and STOT instructions are used together to configure the step sequence.
·
Two or more STOT instructions can be placed on one rung to perform simultaneous sequences.
·
Two or more STIN instructions can be placed on one rung in parallel or in series to perform loop or
convergence of sequences. (Max. 11 STIN instructions on one rung)
·
To perform the conditional branch (sequence selection), separate the rungs as follows.
This limitation is applied to T1 version 1.00 only.
[ STIN
A ]
| |
[ STOT
B ]
[ STIN
A ]
| |
[ STOT
B ]
| |
[ STOT
C ]
[ STIN
A ]
| |
[ STOT
C ]
Not allowed
Available