6F3B0250
Basic Hardware and Function
235
7. Instructions
FUN 154
CLND
Set calendar
Expression
Input
-
[
A
CLND ]
-
Output
Function
When the input is ON, the built-in clock/calendar is set to the date and time specified by 6 registers
starting with
A. If an invalid data is contained in the registers, the operation is not executed and the
output is turned ON.
Execution condition
Input
Operation
Output
OFF
No operation
OFF
ON
Execution (data is valid))
OFF
No execution (data is not valid)
ON
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW
T
C
D
I
J
K
A
Start of table
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Example
When R020 is ON, the clock/calendar is set according to the data of D0050 to D0055, and the
output is OFF (R0031 is OFF).
If D0050 to D0055 contains invalid data, the setting operation is not executed and the output is
turned ON (R0031 comes ON).
F
8 7
0
Allowable data range (2-digit BCD)
D0050
H00
Year
H00 to H99 (1990 - 2089)
D0051
H00
Month
H01 to H12
D0052
H00
Day
H01 to H31
Calendar
D0053
H00
Hour
H00 to H23
LSI
D0054
H00
Minute
H00 to H59
D0055
H00
Second
H00 to H59
Note
·
The day of the week is automatically.
T1S only