6F3B0250
182
T1/T1S User’s Manual
7. Instructions
FUN 068
SHR1
1 bit shift right
Expression
Input
-
[ SHR1
A
]
-
Output
Function
When the input is ON, the data of register
A is shifted 1 bit to the right (LSB direction). 0 is stored in the
left most bit (MSB). The pushed out bit state is stored in the carry flag (CF = S050). After the operation,
if the right most bit (LSB) is ON, the output is turned ON.
Execution condition
Input
Operation
Output
CF
OFF
No execution
OFF
-
ON
Execution
When LSB = 1
ON
Set or reset
When LSB = 0
OFF
Set or reset
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW
T
C
D
I
J
K
A
Operation data
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Example
When X007 is changed from OFF to ON, the data of RW15 is shifted 1 bit to the right.
The figure below shows an operation example.
(MSB)
(LSB)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
RW15
0 1 0 0 0 0 1 0 1 0 0 0 1 0 1 0
CF
RW15
0 0 1 0 0 0 0 1 0 1 0 0 0 1 0 1
0
(Result)
0
R001 is turned ON
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]