Basic Hardware and Function
271
8. Special I/O Functions
The table below summarizes the mode setting data of each function. In the table,
‘
-
’ means do not care.
Variable input filter constant
SW16
F E D C B A 9 8 7 6 5 4 3 2 1 0
Use
1 0
- - - -
0 0
- -
0 0
- - - -
High speed counter
SW16
F E D C B A 9 8 7 6 5 4 3 2 1 0
Single phase
Channel 1 only
-
0 0 1 0 0 0 0 0 0 0 0 0 0 1 1
up-counter
Channel 2 only
-
0 1 0 0 0 0 0 0 0 0 0 0 0 1 1
Both channels
-
0 1 1 0 0 0 0 0 0 0 0 0 0 1 1
Single phase
Channel 1 only
-
0 0 1 0 1 0 0 0 0 0 0 0 0 1 1
speed-counter
Channel 2 only
-
0 1 0 0 1 0 0 0 0 0 0 0 0 1 1
Both channels
-
0 1 1 0 1 0 0 0 0 0 0 0 0 1 1
Quadrature bi-pulse counter
-
0 0 0 1 0 0 0 0 0 0 0 0 0 1 1
Interrupt input function
SW16
F E D C B A 9 8 7 6 5 4 3 2 1 0
Interrupt 1 only Rising (OFF to ON)
-
0 0 1 0 0 0 0 0 0 0 0 0 1 0 1
Falling (ON to OFF)
-
0 0 1 0 0 0 0 0 0 0 0 1 0 0 1
Interrupt 2 only Rising (OFF to ON)
-
0 1 0 0 0 0 0 0 1 0 0 0 0 0 1
Falling (ON to OFF)
-
0 1 0 0 0 0 0 1 0 0 0 0 0 0 1
Both interrupts No.1 = Rising, No.2 = Rising
-
0 1 1 0 0 0 0 0 1 0 0 0 1 0 1
1 and 2
No.1 = Rising, No.2 = Falling
-
0 1 1 0 0 0 0 1 0 0 0 0 1 0 1
No.1 = Falling, No.2 = Rising
-
0 1 1 0 0 0 0 0 1 0 0 1 0 0 1
No.1 = Falling, No.2 = Falling
-
0 1 1 0 0 0 0 1 0 0 0 1 0 0 1
Pulse output function
SW26
F E D C B A 9 8 7 6 5 4 3 2 1 0
CW/CCW method
- - -
0 0 0 0 0 0 0 0 0 0 0 1 1
Pulse/Direction (PLS/DIR) method
- - -
0 0 0 0 0 0 0 0 0 0 1 1 1
PWM output function
SW26
F E D C B A 9 8 7 6 5 4 3 2 1 0
Use
- - -
0 0 0 0 0 0 0 0 0 0 0 0 1
For example, the following programs can be used to select the quadrature bi-pulse
counter.
or
(H0803)