6F3B0250
48
T1/T1S User’s Manual
2. Specifications
2.4 I/O specifications
2.4.1
T1-16
····
T1-16 input specifications
Item
Specifications
DC input type
AC input type
AC power type
DC power type
Input type
Dry contact input,
current source or
sink
*1
DC input,
current source or
sink
*2
AC input
Number of input
points
8 points (8 points/common)
8 points (8 points/common)
Rated input voltage Supplied from
T1-16
(24 Vdc,
±
10 %)
24 Vdc,
+10/-15%
100 - 120 Vac, +10/-15 %,
50/60 Hz
Rated input current 7 mA (at 24 Vdc)
7 mA (at 100 Vac)
ON level
Contact close
(max. 1.2 k
W
)
Min. ON
voltage: 15 Vdc
Min. ON voltage: 80 Vac
OFF level
Contact open
(min. 20 k
W
)
Min. OFF
voltage: 5 Vdc
Max. OFF voltage: 30 Vac
ON delay time
0 to 15 ms
*3
25 ms or less + user setting
*4
OFF delay time
0 to 15 ms
*3
30 ms or less + user setting
*4
Input signal display LED display for all points, lit at ON, internal logic side
External connection Terminal block (fixed), M3.5
Withstand voltage
1500 Vac, 1 minute (between internal and external circuits)
Internal circuit
*1: The input current direction (source or sink) of the dry contact input can be selected by the
internal jumper plug. (Factory setting = current source) Refer to section 3.1.
3 side: current flows from input terminal to (
-
) terminal (current source)
1 side: current flows from (+) terminal to input terminal (current sink)
*2: The jumper plug of the DC power supply type must be set to 1 side.
*3: The input ON/OFF delay time of the DC input type can be changed by user. The setting range is
0 to 15 ms. (Default value = 10 ms) Refer to section 8.2.
*4: The input ON/OFF delay time of the AC input can be extended by user. The extension setting
range is 0 to 15 ms. (Default value = 10 ms) Resulting the default delay times are 35 ms (ON
delay) and 40 ms (OFF delay). Refer to section 8.2.
LED
+
-
24 Vdc
(AC power type only)
*1, *2
1
3
7
0
LED
C
7
0
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]