7. Instructions
FUN 025
TMOV
Table transfer
Expression
Input
-
[
A
TMOV (
n
)
B
]
-
Output
Function
When the input is ON, the data of
n registers starting with A are transferred to n registers starting with
B in a block. The allowable range of the table size n is 1 to 1024 words.
Execution condition
Input
Operation
Output
OFF
No execution
OFF
ON
Execution
ON
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW
T
C
D
I
J
K
A
Start of source
Ö
Ö
Ö
Ö
Ö
Ö
Ö
n
Table size
1 - 1024
B
Start of
destination
Ö
Ö
Ö
Ö
Ö
Ö
Example
When R010 is ON, the data of D0500 to D0509 (10 registers) are block transferred to D1000 to
D1009, and the output is turned ON.
D0500
1111
D1000
1111
D0501
2222
D1001
2222
D0502
3333
Block transfer
D1002
3333
10 registers
D0509
12345
D1009
12345
Note
·
The source and destination tables can be overlapped.
T1S only