Installation

•  When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must be 

used.

•  Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is not 

enough, the unit may fall down resulting in injury.

•  Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may 

cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other trouble.

•  Carry out the speci

fi

 ed installation work to guard against the possibility of high winds and earthquake. If the air 

conditioner is not installed appropriately, a unit may topple over or fall down, causing an accident.

•  If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas 

comes in contact with 

fi

 re, noxious gas may generate.

•  Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.

Refrigerant piping

•  Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is 

operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over 
pressurized, which may cause a injury.

• Tighten the 

fl

 are nut with a torque wrench in the speci

fi

 ed manner. Excessive tighten of the 

fl

 are nut may cause a crack 

in the 

fl

 are nut after a long period, which may result in refrigerant leakage.

•  After the installation work, con

fi

 rm that refrigerant gas does not leak. If refrigerant gas leaks into the room and 

fl

 ows near 

fi

 re source, such as a cooking range, noxious gas may be generated.

•  When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the 

air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air 
completely may cause the air conditioner to malfunction.

•  Nitrogen gas must be used for the airtight test.
•  The charge hose must be connected in such a way that it is not slack.

Electrical wiring

•  Only a quali

fi

 ed installer (*1) or quali

fi

 ed service person (*1) is allowed to carry out the electrical work of the air 

conditioner. Under no circumstances must this work be done by an unquali

fi

 ed individual since failure to carry out the 

work properly may result in electric shocks and/or electrical leaks. 

•  To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide 

protection for electricians, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this 
protective gear may result in electric shocks. 

•  Use wiring that meets the speci

fi

 cations in the Installation Manual and the stipulations in the local regulations and laws. 

Use of wiring which does not meet the speci

fi

 cations may give rise to electric shocks, electrical leakage, smoking and/

or a 

fi

 re. 

•  Connect earth wire. (Grounding work)
•  Incomplete grounding causes an electric shock. 
•  Do not connect earth wires to gas pipes, water pipes, and lightning conductor or telephone earth wires. 
•  After completing the repair or relocation work, check that the earth wires are connected properly. 
•  Install a circuit breaker that meets the speci

fi

 cations in the installation manual and the stipulations in the local regulations 

and laws. 

•  Install the circuit breaker where it can be easily accessed by the agent. 
•  When installing the circuit breaker outdoors, install one which is designed to be used outdoors. 
•  Under no circumstances the power wire must not be extended. Connection trouble in the places where the wire is 

extended may give rise to smoking and/or a 

fi

 re. 

•  Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. 

Failure to do so may result in electrocution or short circuit. 

Test run 

•  Before operating the air conditioner after having completed the work, check that the electrical control box cover of the 

indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may 
receive an electric shock if the power is turned on without 

fi

 rst conducting these checks. 

•  If there is any kind of trouble (such as an error display has appeared, smell of burning, abnormal sounds, the air 

conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner 
yourself but set the circuit breaker to the OFF position, and contact a quali

fi

 ed service person (*1). Take steps to ensure 

that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until quali

fi

 ed 

service person (*1) arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to 
escalate or result in electric shocks or other trouble. 

•  After the work has 

fi

 nished, use an insulation tester set (500 V Megger) to check the resistance is 1 M

Ω

 or more 

between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster 
such as a leak or electric shock is caused at user’s side. 

•  Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water 

drainage. Then conduct a test run to check that the air conditioner is operating properly. 

Explanations given to user 

•  Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know 

where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air 
conditioner. 

•  If the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact 

a quali

fi

 ed service person (*1) to have the repairs done. Do not set the circuit breaker to the ON position until the repairs 

are completed. 

•  After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.

Relocation 

•  Only a quali

fi

 ed installer (*1) or quali

fi

 ed service person (*1) is allowed to relocate the air conditioner. It is dangerous for 

the air conditioner to be relocated by an unquali

fi

 ed individual since a 

fi

 re, electric shocks, injury, water leakage, noise 

and/or vibration may result. 

•  When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. 

Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or 
other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly 
resulting in rupture, injury or other trouble.

7-EN 

8-EN

 CAUTION

New refrigerant air conditioner installation 

• 

This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer. 

•  The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is 

approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also 
been changed. Therefore, do not let water, dust, former refrigerant, or refrigerating oil enter the refrigerating cycle during 
installation work. 

•  To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the 

main unit and installation tools are changed from those for the conventional refrigerant. 

•  Accordingly the exclusive tools are required for the new refrigerant (R410A). 
•  For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not 

enter. 

To disconnect the appliance from main power supply. 

•  This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 

3 mm. 

The installation fuse (all types can be used) must be used for the power supply line of this conditioner. 

(*1) Refer to the “De

fi

 nition of Quali

fi

 ed Installer or Quali

fi

 ed Service Person.”

Summary of Contents for MMC-AP0157HP-E (TR)

Page 1: ...NDITIONER MULTI TYPE Installation Manual For commercial use English Indoor Unit Model name Ceiling Type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E ...

Page 2: ... 10 Maintenance 17 11 Troubleshooting 18 12 Specifications 23 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly ref...

Page 3: ...ted to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air cond...

Page 4: ...ndertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and the...

Page 5: ...or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If there is any kind of trouble such as an error...

Page 6: ...ps or other moving conveyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditi...

Page 7: ...ess remote controller kit sold separately The signal of the wireless type remote controller can be received within approx 8 m This distance is a criterion and varies a little according to capacity of the battery To prevent malfunction select a place where is not affected by a fluorescent lamp or direct sunlight Two wireless type indoor units can be set in a room 4 Installation Model MMC Possible i...

Page 8: ... Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the External dimensions Installation of remote controller Sold separately For installation of the remote controller follow the Installation Manual attached with the remote controller Pull out the remote controller cord together with the refrigerant pipe or drain pipe Pass the remote cont...

Page 9: ...ase of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking out the drain pipe from the upper side use a drain up kit sold separately Open the upper pipe draw out port Knockout hole shown in the external dimensions Make the diagonally shaded hole when you do not use the Elbow Piping Kit Make only this knockout hole when you use the separately ...

Page 10: ...any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit Be absolutely sure to use the flexible hose provided for the connections with the drain pipe connecting port Adhesive agents cannot be used for the drain pipe...

Page 11: ...e of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain up When a down gradient cannot be secured for the drain pipe drain up piping is possible The height of the drain pipe must be 600 mm or less from the underside of the indoor unit When Drain Pump Kit sold separately is inst...

Page 12: ... the refrigerant of specified amount REQUIREMENT Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunc...

Page 13: ... of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 IEC 57 CAUTION If incorrect incomplete wiring is carried out it will cause an e...

Page 14: ...wer supply wiring fuse rating for indoor units should be selected by the accumulated total current values of the indoor units Power supply wiring Below 50 m 2 5 mm2 Control wiring Central controller wiring 2 core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring To prevent noise trouble use 2 core shield wire The length of the co...

Page 15: ...Remote controller Indoor unit Indoor unit Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Earth leakage breaker Outdoor Power supply 380 415 V 50 Hz 380 V 60 Hz 1 Push and hold button and TEMP button simultaneously for at least 4 seconds After a while the display flashes as shown in the figure Confirm that the CODE No is 01 I...

Page 16: ...edure and wiring method of the individual line Identical refrigerant line system refer to Electrical connection in this Manual Wiring between indoor units in a group is performed in the following procedure Connect the indoor units by connecting the remote controller inter unit wires from the remote controller terminal blocks A B of the indoor unit connected with a remote controller to the remote c...

Page 17: ...ble for trial runs To perform a test run set the unit to heating mode with the remote controller The unit might not operate in heating mode however depending on temperature conditions 1 Hold down the TEMPORARY button for over 10 seconds With a beep sound the unit is set to the forced cooling mode In approximately three minutes it is forced to start in cooling mode Determine that cool air comes out...

Page 18: ...eck if there is any clogging or drain water is polluted Maintenance List Part Unit Check visual auditory Maintenance Heat exchanger Indoor outdoor Dust dirt clogging scratches Wash the heat exchanger when it is clogged Fan motor Indoor outdoor Sound Take appropriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace...

Page 19: ...log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to s...

Page 20: ...tion circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master r...

Page 21: ...ALT Ps sensor error I F F24 F24 ALT Pd sensor error I F F29 SIM Indoor unit other error Indoor unit F31 F31 SIM Indoor unit EEPROM error I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04...

Page 22: ... unit L31 Extended I C error I F P01 ALT Indoor fan motor error Indoor unit P03 P03 ALT Discharge temp TD1 error I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation IPDU P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC volta...

Page 23: ...06 Comp 2 Comp 3 07 Comp 1 Comp 2 Comp 3 08 Fan 09 Comp 1 Fan 0A Comp 2 Fan 0B Comp 1 Comp 2 Fan 0C Comp 3 Fan 0D Comp 1 Comp 3 Fan 0E Comp 2 Comp 3 Fan 0F Comp 1 Comp 2 Comp 3 Fan Error detected by TCC LINK central control device Check code Wireless remote controller Check code name Judging device Wired remote controller display Outdoor unit 7 segment display Sensor block display of receiving uni...

Page 24: ...ited Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies w...

Page 25: ... Min volume of the indoor unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device Important 2 When there is an effective opening with the adjacent room for venti...

Page 26: ...1114652499 ...