Work using double spanner

Right

A

Upper

Back

Refrigerant piping

 

Take out direction of 
refrigerant pipe

•  The refrigerant pipe connecting sections are located 

as shown below. (Pipes can be taken out from one of 
the three directions.)

•  Make a pipe knockout hole, referring to the section 

“Pipe knockout hole”.

*  When Drain Pump Kit (sold separately) is installed, a 

refrigerant pipe can only be taken out from upper direction. 

 

Connecting refrigerant piping 

Flaring diameter size: A (Unit: mm) 

*  In case of 

fl

 aring for R410A with the conventional 

fl

 are tool, pull it out approx. 0.5 mm more than that 

for R22 to adjust to the speci

fi

 ed 

fl

 are size. The 

copper pipe gauge is useful for adjusting projection 
margin size.

•  The sealed gas was sealed at the atmospheric 

pressure so when the 

fl

 are nut is removed, there 

will no “whooshing” sound: This is normal and is not 
indicative of trouble.

•  Use two wrenches to connect the indoor unit pipe. 

•  Use the tightening torque levels as listed in the table 

below.

Outer dia. of 

connecting pipe (mm)

Tightening torque (N•m)

6.4

14 to 18 (1.4 to 1.8 kgf•m)

9.5

34 to 42 (3.4 to 4.2 kgf•m)

12.7

49 to 61 (4.9 to 6.1 kgf•m)

15.9

63 to 77 (6.3 to 7.7 kgf•m)

•  Tightening torque of 

fl

 are pipe connections. 

Pressure of R410A is higher than that of R22. 
(Approx. 1.6 times) Therefore, using a torque 
wrench, tighten the 

fl

 are pipe connecting sections 

which connect the indoor and outdoor units of the 
speci

fi

 ed tightening torque. 

Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.

 

Evacuation 

Perform vacuuming from the charge port of valve of 
the outdoor unit by using a vacuum pump. 
For details, follow to the Installation Manual attached to 
the outdoor unit. 
•  Do not use the refrigerant sealed in the outdoor unit 

for evacuation.

REQUIREMENT

For the tools such as charge hose, use those 
manufactured exclusively for R410A.

Refrigerant amount to be added 

For addition of the refrigerant, add refrigerant “R410A” 
referring to the attached Installation Manual of outdoor 
unit. 
Use a scale to charge the refrigerant of speci

fi

 ed 

amount. 

REQUIREMENT

•  Charging an excessive or too little amount of 

refrigerant causes a trouble of the compressor. 
Charge the refrigerant of speci

fi

 ed amount. 

•  A personnel who charged the refrigerant should 

write down the pipe length and the added refrigerant 
amount in the F-GAS label of the outdoor unit. It is 
necessary to 

fi

 x the compressor and refrigeration 

cycle malfunction. 

Open the valve fully 

Open the valve of the outdoor unit fully. A 4 mm-
hexagonal wrench is required for opening the valve. 
For details, refer to the Installation Manual attached to 
the outdoor unit. 

Gas leak check 

Check with a leak detector or soap water whether gas 
leaks or not, from the pipe connecting section or cap 
of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC 
refrigerant (R410A, R134a). 

21-EN 

22-EN 

Outer dia. of copper pipe

A

+0
–0.4

6.4

9.1

9.5

13.2

12.7

16.6

15.9

19.7

 

Permissible piping length and 
height difference 

They vary depending on the outdoor unit. For details, 
refer to the Installation Manual attached to the outdoor 
unit.

 

Pipe size

Model MMC- 

Pipe size (mm)

Gas side

Liquid side

AP015 to AP018 

Ø12.7

Ø6.4

AP024 to AP056 

Ø15.9

Ø9.5

Flaring

1

Cut the pipe with a pipe cutter. 

Remove burrs completely. (Remaining burrs may 
cause gas leakage.)

2

Insert a 

fl

 are nut into the pipe, and 

fl

 are the 

pipe.

Use the 

fl

 are nut provided with the unit or the 

one used for the R410A refrigerant. The 

fl

 aring 

dimensions for R410A are different from the ones 
used for the conventional R22 refrigerant. A new 

fl

 are tool manufactured for use with the R410A 

refrigerant is recommended, but the conventional 
tool can still be used if the projection margin of 
the copper pipe is adjusted to be as shown in the 
following table.

Projection margin in 

fl

 aring: B (Unit: mm)

Outer dia. of 

copper pipe

R410A tool used

Conventional 

tool used

6.4, 9.5

0 to 0.5

1.0 to 1.5

12.7, 15.9

B

 CAUTION

Tightening with an excessive torque may crack the nut 
depending on installation conditions.

 CAUTION

When the refrigerant pipe is long, provide support 
brackets at intervals of 2.5 m to 3 m to clamp the 
refrigerant pipe. Otherwise, abnormal sound may be 
generated.
Use the 

fl

 are nut attached with the indoor unit or 

R410A 

fl

 are nut.

Summary of Contents for MMC-AP0157HP-E (TR)

Page 1: ...NDITIONER MULTI TYPE Installation Manual For commercial use English Indoor Unit Model name Ceiling Type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E ...

Page 2: ... 10 Maintenance 17 11 Troubleshooting 18 12 Specifications 23 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly ref...

Page 3: ...ted to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air cond...

Page 4: ...ndertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and the...

Page 5: ...or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If there is any kind of trouble such as an error...

Page 6: ...ps or other moving conveyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditi...

Page 7: ...ess remote controller kit sold separately The signal of the wireless type remote controller can be received within approx 8 m This distance is a criterion and varies a little according to capacity of the battery To prevent malfunction select a place where is not affected by a fluorescent lamp or direct sunlight Two wireless type indoor units can be set in a room 4 Installation Model MMC Possible i...

Page 8: ... Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the External dimensions Installation of remote controller Sold separately For installation of the remote controller follow the Installation Manual attached with the remote controller Pull out the remote controller cord together with the refrigerant pipe or drain pipe Pass the remote cont...

Page 9: ...ase of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking out the drain pipe from the upper side use a drain up kit sold separately Open the upper pipe draw out port Knockout hole shown in the external dimensions Make the diagonally shaded hole when you do not use the Elbow Piping Kit Make only this knockout hole when you use the separately ...

Page 10: ...any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit Be absolutely sure to use the flexible hose provided for the connections with the drain pipe connecting port Adhesive agents cannot be used for the drain pipe...

Page 11: ...e of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain up When a down gradient cannot be secured for the drain pipe drain up piping is possible The height of the drain pipe must be 600 mm or less from the underside of the indoor unit When Drain Pump Kit sold separately is inst...

Page 12: ... the refrigerant of specified amount REQUIREMENT Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunc...

Page 13: ... of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 IEC 57 CAUTION If incorrect incomplete wiring is carried out it will cause an e...

Page 14: ...wer supply wiring fuse rating for indoor units should be selected by the accumulated total current values of the indoor units Power supply wiring Below 50 m 2 5 mm2 Control wiring Central controller wiring 2 core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring To prevent noise trouble use 2 core shield wire The length of the co...

Page 15: ...Remote controller Indoor unit Indoor unit Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Earth leakage breaker Outdoor Power supply 380 415 V 50 Hz 380 V 60 Hz 1 Push and hold button and TEMP button simultaneously for at least 4 seconds After a while the display flashes as shown in the figure Confirm that the CODE No is 01 I...

Page 16: ...edure and wiring method of the individual line Identical refrigerant line system refer to Electrical connection in this Manual Wiring between indoor units in a group is performed in the following procedure Connect the indoor units by connecting the remote controller inter unit wires from the remote controller terminal blocks A B of the indoor unit connected with a remote controller to the remote c...

Page 17: ...ble for trial runs To perform a test run set the unit to heating mode with the remote controller The unit might not operate in heating mode however depending on temperature conditions 1 Hold down the TEMPORARY button for over 10 seconds With a beep sound the unit is set to the forced cooling mode In approximately three minutes it is forced to start in cooling mode Determine that cool air comes out...

Page 18: ...eck if there is any clogging or drain water is polluted Maintenance List Part Unit Check visual auditory Maintenance Heat exchanger Indoor outdoor Dust dirt clogging scratches Wash the heat exchanger when it is clogged Fan motor Indoor outdoor Sound Take appropriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace...

Page 19: ...log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to s...

Page 20: ...tion circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master r...

Page 21: ...ALT Ps sensor error I F F24 F24 ALT Pd sensor error I F F29 SIM Indoor unit other error Indoor unit F31 F31 SIM Indoor unit EEPROM error I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04...

Page 22: ... unit L31 Extended I C error I F P01 ALT Indoor fan motor error Indoor unit P03 P03 ALT Discharge temp TD1 error I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation IPDU P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC volta...

Page 23: ...06 Comp 2 Comp 3 07 Comp 1 Comp 2 Comp 3 08 Fan 09 Comp 1 Fan 0A Comp 2 Fan 0B Comp 1 Comp 2 Fan 0C Comp 3 Fan 0D Comp 1 Comp 3 Fan 0E Comp 2 Comp 3 Fan 0F Comp 1 Comp 2 Comp 3 Fan Error detected by TCC LINK central control device Check code Wireless remote controller Check code name Judging device Wired remote controller display Outdoor unit 7 segment display Sensor block display of receiving uni...

Page 24: ...ited Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies w...

Page 25: ... Min volume of the indoor unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device Important 2 When there is an effective opening with the adjacent room for venti...

Page 26: ...1114652499 ...

Reviews: