  Selection of installation place 

Avoid installing in the following places. 

Select a location for the indoor unit where the cool or warm air will circulate evenly. 
Avoid installation in the following kinds of locations. 

• 

Saline area (coastal area). 

• 

Locations with acidic or alkaline atmospheres (such as areas with hot springs, factories where chemicals or 
pharmaceuticals are made and places where the exhaust air from combustion appliances will be sucked into the 
unit). 
Doing so may cause the heat exchanger (its aluminum 

fi

 ns and copper pipes) and other parts to become 

corroded. 

• 

Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior 
of the air conditioner, it may spontaneously combust and start a 

fi

 re. 

• 

Locations with atmospheres with mist of cutting oil or other types of machine oil. 
Doing so may cause the heat exchanger to become corroded, mists caused by the blockage of the heat 
exchanger to be generated, the plastic parts to be damaged, the heat insulators to peel off, and other such 
problems to result. 

• 

Locations where vapors from food oils are formed (such as kitchens where food oils are used). 
Blocked 

fi

 lters may cause the air conditioner’s performance to deteriorate, condensation to form, the plastic 

parts to be damaged, and other such problems to result. 

• 

Locations near obstructions such as ventilation openings or lighting 

fi

 xtures where the 

fl

 ow of the blown air will 

be disrupted (a disruption of the air 

fl

 ow may cause the air conditioner’s performance to deteriorate or the unit to 

shut down). 

• 

Locations where an in-house power generator is used for the power supply. 
The power line frequency and voltage may 

fl

 uctuate, and the air conditioner may not work properly as a result. 

• 

On truck cranes, ships or other moving conveyances. 

• 

The air conditioner must not be used for special applications (such as for storing food, plants, precision 
instruments or art works). 
(The quality of the items stored may be degraded.) 

• 

Locations where high frequencies are generated (by inverter equipment, in-house power generators, medical 
equipment or communication equipment). 
(Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment’s operation.) 

• 

Locations where there is anything under the unit installed that would be compromised by wetness. 
(If the drain has become blocked or when the humidity is over 80 %, condensation from the indoor unit will drip, 
possibly causing damage to anything underneath.) 

• 

In the case of the wireless type of system, rooms with the inverter type of 

fl

 uorescent lighting or locations 

exposed to direct sunlight. 
(The signals from the wireless remote controller may not be sensed.) 

• 

Locations where organic solvents are being used. 

• 

The air conditioner cannot be used for lique

fi

 ed carbonic acid cooling or in chemical plants. 

• 

Location near doors or windows where the air conditioner may come into contact with high-temperature, high-
humidity outdoor air. 
(Condensation may occur as a result.) 

• 

Locations where special sprays are used frequently. 

9-EN 

10-EN

Part name 

Q’ty 

 Shape 

Usage

Installation Manual 

1

 This manual 

(Hand over to customers) 
(For other languages that do not appear in this Installation 
Manual, please refer to the enclosed CD-R.) 

CD-ROM 1

-

Installation 

Manual 

Heat insulating pipe 

2

For heat insulation of pipe connecting section 

Washer 

4

 M10 × Ø25

For holding down unit 

Hose band 

2

For connecting drain pipe 

Drain hose 

1

For connecting drain pipe 

Bushing 1

For protection of edge at power taking-in port 

Heat insulator 

1

For heat insulation of drain hose (10 t × 190 × 190) 

Heat insulator of top plate

1

For upper pipe hole of indoor unit (6 t × 120 × 160) 

Banding band 

6

For heat insulation of pipe connecting section (n=4) and 
drain hose heat insulator (n=2). 

 

Summary of Contents for MMC-AP0157HP-E (TR)

Page 1: ...NDITIONER MULTI TYPE Installation Manual For commercial use English Indoor Unit Model name Ceiling Type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E ...

Page 2: ... 10 Maintenance 17 11 Troubleshooting 18 12 Specifications 23 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly ref...

Page 3: ...ted to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air cond...

Page 4: ...ndertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and the...

Page 5: ...or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If there is any kind of trouble such as an error...

Page 6: ...ps or other moving conveyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditi...

Page 7: ...ess remote controller kit sold separately The signal of the wireless type remote controller can be received within approx 8 m This distance is a criterion and varies a little according to capacity of the battery To prevent malfunction select a place where is not affected by a fluorescent lamp or direct sunlight Two wireless type indoor units can be set in a room 4 Installation Model MMC Possible i...

Page 8: ... Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the External dimensions Installation of remote controller Sold separately For installation of the remote controller follow the Installation Manual attached with the remote controller Pull out the remote controller cord together with the refrigerant pipe or drain pipe Pass the remote cont...

Page 9: ...ase of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking out the drain pipe from the upper side use a drain up kit sold separately Open the upper pipe draw out port Knockout hole shown in the external dimensions Make the diagonally shaded hole when you do not use the Elbow Piping Kit Make only this knockout hole when you use the separately ...

Page 10: ...any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit Be absolutely sure to use the flexible hose provided for the connections with the drain pipe connecting port Adhesive agents cannot be used for the drain pipe...

Page 11: ...e of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain up When a down gradient cannot be secured for the drain pipe drain up piping is possible The height of the drain pipe must be 600 mm or less from the underside of the indoor unit When Drain Pump Kit sold separately is inst...

Page 12: ... the refrigerant of specified amount REQUIREMENT Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunc...

Page 13: ... of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 IEC 57 CAUTION If incorrect incomplete wiring is carried out it will cause an e...

Page 14: ...wer supply wiring fuse rating for indoor units should be selected by the accumulated total current values of the indoor units Power supply wiring Below 50 m 2 5 mm2 Control wiring Central controller wiring 2 core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring To prevent noise trouble use 2 core shield wire The length of the co...

Page 15: ...Remote controller Indoor unit Indoor unit Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Earth leakage breaker Outdoor Power supply 380 415 V 50 Hz 380 V 60 Hz 1 Push and hold button and TEMP button simultaneously for at least 4 seconds After a while the display flashes as shown in the figure Confirm that the CODE No is 01 I...

Page 16: ...edure and wiring method of the individual line Identical refrigerant line system refer to Electrical connection in this Manual Wiring between indoor units in a group is performed in the following procedure Connect the indoor units by connecting the remote controller inter unit wires from the remote controller terminal blocks A B of the indoor unit connected with a remote controller to the remote c...

Page 17: ...ble for trial runs To perform a test run set the unit to heating mode with the remote controller The unit might not operate in heating mode however depending on temperature conditions 1 Hold down the TEMPORARY button for over 10 seconds With a beep sound the unit is set to the forced cooling mode In approximately three minutes it is forced to start in cooling mode Determine that cool air comes out...

Page 18: ...eck if there is any clogging or drain water is polluted Maintenance List Part Unit Check visual auditory Maintenance Heat exchanger Indoor outdoor Dust dirt clogging scratches Wash the heat exchanger when it is clogged Fan motor Indoor outdoor Sound Take appropriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace...

Page 19: ...log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to s...

Page 20: ...tion circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master r...

Page 21: ...ALT Ps sensor error I F F24 F24 ALT Pd sensor error I F F29 SIM Indoor unit other error Indoor unit F31 F31 SIM Indoor unit EEPROM error I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04...

Page 22: ... unit L31 Extended I C error I F P01 ALT Indoor fan motor error Indoor unit P03 P03 ALT Discharge temp TD1 error I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation IPDU P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC volta...

Page 23: ...06 Comp 2 Comp 3 07 Comp 1 Comp 2 Comp 3 08 Fan 09 Comp 1 Fan 0A Comp 2 Fan 0B Comp 1 Comp 2 Fan 0C Comp 3 Fan 0D Comp 1 Comp 3 Fan 0E Comp 2 Comp 3 Fan 0F Comp 1 Comp 2 Comp 3 Fan Error detected by TCC LINK central control device Check code Wireless remote controller Check code name Judging device Wired remote controller display Outdoor unit 7 segment display Sensor block display of receiving uni...

Page 24: ...ited Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies w...

Page 25: ... Min volume of the indoor unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device Important 2 When there is an effective opening with the adjacent room for venti...

Page 26: ...1114652499 ...

Reviews: