– 14 – 

Terminal block for 
remote controller 
wiring of indoor unit

Remote controller wire (Locally procured)

Remote 
controller 
unit

Remote controller wire 

Run the remote 
controller wire through 
the cord clamp.

(* Display content varies with the indoor 
unit model.) 

8

 Applicable 

controls 

 

Remote controller wiring

 

Wiring between indoor and outdoor units

NOTE

An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the 
header unit.

 Wiring example

 

 Address setup

Set up the addresses as per the Installation Manual supplied with the outdoor unit.

Strip off approx. 9 mm the wire to be connected.

Wiring diagram 

Terminal block 

Remote controller 
wire

 

Basic procedure for changing 
settings 

Change the settings while the air conditioner is not 
working. 

(Stop the air conditioner before making 

settings.) 

 CAUTION

Set only the CODE No. shown in the following table: 
Do NOT set any other CODE No. 
If a CODE No. not listed is set, it may not be possible 
to operate the air conditioner or other trouble with the 
product may result. 
* The displays appearing during the setting process 

differ from the ones for previous remote controllers 
(AMT31E). (There are more CODE No.) 

27-EN 

28-EN 

Outdoor Power supply
380-415 V ~, 50 Hz
380 V ~, 60 Hz

Earth leakage 
breaker

Header outdoor unit

Earth 
terminal

Earth 
terminal

Follower outdoor unit

Indoor unit

Indoor power supply
220-240 V ~, 50 Hz
220 V ~, 60 Hz

Circuit breaker 
power switch

Earth

Earth

Earth

Earth

Indoor unit

Remote controller

Pull box

Pull box

Pull box

Remote controller

Remote controller

Indoor unit

Indoor unit

Control wiring between outdoor units

Control wiring between indoor and outdoor units

Control wiring between indoor units

Earth leakage 
breaker

Outdoor Power supply
380-415 V ~, 50 Hz
380 V ~, 60 Hz

1

Push and hold button 

 and “TEMP.” 

 

button simultaneously for at least 4 seconds. 
After a while, the display 

fl

 ashes as shown in 

the 

fi

 gure. Con

fi

 rm that the CODE No. is [01].

•  If the CODE No. is not [01], push

 

 

button 

to clear the display content, and repeat the 
procedure from the beginning. (No operation 
of the remote controller is accepted for a while 
after

 

 

button is pushed.) 

(While air conditioners are operated under the 
group control, “ALL” is displayed 

fi

 rst. When 

is pushed, the indoor unit number 

displayed following “ALL” is the header unit.) 

REQUIREMENT

When the air conditioner is used for the 

fi

 rst time, it will 

take some moments after the power has been turned 
on before the remote controller becomes available 
for operations: This is normal and is not indicative of 
trouble.
•  Concerning the automatic addresses (The automatic 

addresses are set up by performing operations on 
the outdoor interface circuit board.) 
While the automatic addresses are being set up, 
no remote controller operations can be performed. 
Setup takes up to 10 minutes (usually about 5 
minutes).

•  When the power is turned on after automatic address 

setup.
It takes up to 10 minutes (usually about 3 minutes) 
for the outdoor unit to start operating after the power 
has been turned on.

Before the air conditioner was shipped from the 
factory, all units are set to [STANDARD] (factory 
default). If necessary, change the indoor unit settings. 
The settings are changed by operating the wired 
remote controller.
* The settings cannot be changed using only a wireless 

remote controller, simple remote controller or group 
control remote controller by itself so install a wired 
remote controller separately as well.

Summary of Contents for MMC-AP0157HP-E (TR)

Page 1: ...NDITIONER MULTI TYPE Installation Manual For commercial use English Indoor Unit Model name Ceiling Type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E ...

Page 2: ... 10 Maintenance 17 11 Troubleshooting 18 12 Specifications 23 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly ref...

Page 3: ...ted to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air cond...

Page 4: ...ndertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and the...

Page 5: ...or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If there is any kind of trouble such as an error...

Page 6: ...ps or other moving conveyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditi...

Page 7: ...ess remote controller kit sold separately The signal of the wireless type remote controller can be received within approx 8 m This distance is a criterion and varies a little according to capacity of the battery To prevent malfunction select a place where is not affected by a fluorescent lamp or direct sunlight Two wireless type indoor units can be set in a room 4 Installation Model MMC Possible i...

Page 8: ... Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the External dimensions Installation of remote controller Sold separately For installation of the remote controller follow the Installation Manual attached with the remote controller Pull out the remote controller cord together with the refrigerant pipe or drain pipe Pass the remote cont...

Page 9: ...ase of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking out the drain pipe from the upper side use a drain up kit sold separately Open the upper pipe draw out port Knockout hole shown in the external dimensions Make the diagonally shaded hole when you do not use the Elbow Piping Kit Make only this knockout hole when you use the separately ...

Page 10: ...any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit Be absolutely sure to use the flexible hose provided for the connections with the drain pipe connecting port Adhesive agents cannot be used for the drain pipe...

Page 11: ...e of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain up When a down gradient cannot be secured for the drain pipe drain up piping is possible The height of the drain pipe must be 600 mm or less from the underside of the indoor unit When Drain Pump Kit sold separately is inst...

Page 12: ... the refrigerant of specified amount REQUIREMENT Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunc...

Page 13: ... of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 IEC 57 CAUTION If incorrect incomplete wiring is carried out it will cause an e...

Page 14: ...wer supply wiring fuse rating for indoor units should be selected by the accumulated total current values of the indoor units Power supply wiring Below 50 m 2 5 mm2 Control wiring Central controller wiring 2 core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring To prevent noise trouble use 2 core shield wire The length of the co...

Page 15: ...Remote controller Indoor unit Indoor unit Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Earth leakage breaker Outdoor Power supply 380 415 V 50 Hz 380 V 60 Hz 1 Push and hold button and TEMP button simultaneously for at least 4 seconds After a while the display flashes as shown in the figure Confirm that the CODE No is 01 I...

Page 16: ...edure and wiring method of the individual line Identical refrigerant line system refer to Electrical connection in this Manual Wiring between indoor units in a group is performed in the following procedure Connect the indoor units by connecting the remote controller inter unit wires from the remote controller terminal blocks A B of the indoor unit connected with a remote controller to the remote c...

Page 17: ...ble for trial runs To perform a test run set the unit to heating mode with the remote controller The unit might not operate in heating mode however depending on temperature conditions 1 Hold down the TEMPORARY button for over 10 seconds With a beep sound the unit is set to the forced cooling mode In approximately three minutes it is forced to start in cooling mode Determine that cool air comes out...

Page 18: ...eck if there is any clogging or drain water is polluted Maintenance List Part Unit Check visual auditory Maintenance Heat exchanger Indoor outdoor Dust dirt clogging scratches Wash the heat exchanger when it is clogged Fan motor Indoor outdoor Sound Take appropriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace...

Page 19: ...log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to s...

Page 20: ...tion circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master r...

Page 21: ...ALT Ps sensor error I F F24 F24 ALT Pd sensor error I F F29 SIM Indoor unit other error Indoor unit F31 F31 SIM Indoor unit EEPROM error I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04...

Page 22: ... unit L31 Extended I C error I F P01 ALT Indoor fan motor error Indoor unit P03 P03 ALT Discharge temp TD1 error I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation IPDU P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC volta...

Page 23: ...06 Comp 2 Comp 3 07 Comp 1 Comp 2 Comp 3 08 Fan 09 Comp 1 Fan 0A Comp 2 Fan 0B Comp 1 Comp 2 Fan 0C Comp 3 Fan 0D Comp 1 Comp 3 Fan 0E Comp 2 Comp 3 Fan 0F Comp 1 Comp 2 Comp 3 Fan Error detected by TCC LINK central control device Check code Wireless remote controller Check code name Judging device Wired remote controller display Outdoor unit 7 segment display Sensor block display of receiving uni...

Page 24: ...ited Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies w...

Page 25: ... Min volume of the indoor unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device Important 2 When there is an effective opening with the adjacent room for venti...