background image

2, 4

3

1, 5

– 16 – 

TEMPORARY button 

9

 Test 

run 

 

Before test run

•  Before turning on the power supply, carry out the 

following procedure.
1) Using 500 V-megger, check that resistance of 1 

M

Ω

 or more exists between the terminal block 

of the power supply and the earth (grounding). If 
resistance of less than 1 M

Ω

 is detected, do not 

run the unit.

2) Check the valve of the outdoor unit being opened 

fully.

•  To protect the compressor at activation time, leave 

power-ON for 12 hours or more be for operating.

•  Never press the electromagnetic contactor to forcibly 

perform a test run. (This is very dangerous because 
the protective device does not work.)

•  Before starting a test run, be sure to set addresses 

following the installation manual supplied with the 
outdoor unit.

 

Execute a test run

Operate the unit with the wired remote controller as 
usual. 
For the procedure of the operation, refer to the 
attached Owner’s Manual. 
A forced test run can be executed in the following 
procedure even if the operation stops by thermostat-
OFF. 
In order to prevent a serial operation, the forced test 
run is released after 60 minutes have passed and 
returns to the usual operation. 

 CAUTION

Do not use the forced test run for cases other than the 
test run because it applies an excessive load to the 
devices. 

Wired remote controller

Wireless remote controller 

NOTE

•  Be sure to operate the unit, following the instruction 

manual 

•  Do not run the air conditioner in forced cooling mode 

for a long time since it overloads the air conditioner. 

•  Forced heating is not available for trial runs. To 

perform a test run, set the unit to heating mode with 
the remote controller. The unit might not operate in 
heating mode, however, depending on temperature 
conditions.

1

Hold down the TEMPORARY button for over 10 
seconds. With a beep sound, the unit is set to 
the forced cooling mode. 

In approximately three minutes, it is forced to start 
in cooling mode. Determine that cool air comes 
out of the unit. If the unit won’t start, check the 
wiring.

2

Push the TEMPORARY button again (for about 
one second) to stop a trial run. 

The upper and lower wind direction changing 
blades close, and the unit stops operation. 

Checking remote transmission 

1. Push the ON/OFF button on the remote controller to 

determine that it works properly. 

•  Pushing the TEST button once (for about one 

second) causes the unit to enter auto operation 
mode. Hold down the TEST button for over 10 
seconds to begin forced cooling. 

•  Even if you select cooling with a remote controller, 

the unit does not always perform cooling operation, 
depending on temperature conditions. Check the 
wiring and piping of the indoor and outdoor units in 
forced cooling mode. 

31-EN 

32-EN 

1

Push 

 button for 4 seconds or more. 

[TEST] is displayed on the display part and 
the selection of mode in the test mode is 
permitted. 

2

Push 

 button.

3

Select the operation mode with 

 button, 

[  Cool] or [

 Heat].

•  Do not run the air conditioner in a mode other 

than [  Cool] or [

 Heat].

•  The temperature controlling function does not 

work during test run.

•  The detection of error is performed as usual.

4

After the test run, push 

 button to stop 

a test run.

(Display part is same as procedure 

1

.)

5

Push 

 button to cancel (release from) the 

test run mode.

([TEST] disappears on the display and the status 
returns to a normal.)

Summary of Contents for MMC-AP0157HP-E (TR)

Page 1: ...NDITIONER MULTI TYPE Installation Manual For commercial use English Indoor Unit Model name Ceiling Type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E ...

Page 2: ... 10 Maintenance 17 11 Troubleshooting 18 12 Specifications 23 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly ref...

Page 3: ...ted to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air cond...

Page 4: ...ndertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and the...

Page 5: ...or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If there is any kind of trouble such as an error...

Page 6: ...ps or other moving conveyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditi...

Page 7: ...ess remote controller kit sold separately The signal of the wireless type remote controller can be received within approx 8 m This distance is a criterion and varies a little according to capacity of the battery To prevent malfunction select a place where is not affected by a fluorescent lamp or direct sunlight Two wireless type indoor units can be set in a room 4 Installation Model MMC Possible i...

Page 8: ... Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the External dimensions Installation of remote controller Sold separately For installation of the remote controller follow the Installation Manual attached with the remote controller Pull out the remote controller cord together with the refrigerant pipe or drain pipe Pass the remote cont...

Page 9: ...ase of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking out the drain pipe from the upper side use a drain up kit sold separately Open the upper pipe draw out port Knockout hole shown in the external dimensions Make the diagonally shaded hole when you do not use the Elbow Piping Kit Make only this knockout hole when you use the separately ...

Page 10: ...any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit Be absolutely sure to use the flexible hose provided for the connections with the drain pipe connecting port Adhesive agents cannot be used for the drain pipe...

Page 11: ...e of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain up When a down gradient cannot be secured for the drain pipe drain up piping is possible The height of the drain pipe must be 600 mm or less from the underside of the indoor unit When Drain Pump Kit sold separately is inst...

Page 12: ... the refrigerant of specified amount REQUIREMENT Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunc...

Page 13: ... of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 IEC 57 CAUTION If incorrect incomplete wiring is carried out it will cause an e...

Page 14: ...wer supply wiring fuse rating for indoor units should be selected by the accumulated total current values of the indoor units Power supply wiring Below 50 m 2 5 mm2 Control wiring Central controller wiring 2 core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring To prevent noise trouble use 2 core shield wire The length of the co...

Page 15: ...Remote controller Indoor unit Indoor unit Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Earth leakage breaker Outdoor Power supply 380 415 V 50 Hz 380 V 60 Hz 1 Push and hold button and TEMP button simultaneously for at least 4 seconds After a while the display flashes as shown in the figure Confirm that the CODE No is 01 I...

Page 16: ...edure and wiring method of the individual line Identical refrigerant line system refer to Electrical connection in this Manual Wiring between indoor units in a group is performed in the following procedure Connect the indoor units by connecting the remote controller inter unit wires from the remote controller terminal blocks A B of the indoor unit connected with a remote controller to the remote c...

Page 17: ...ble for trial runs To perform a test run set the unit to heating mode with the remote controller The unit might not operate in heating mode however depending on temperature conditions 1 Hold down the TEMPORARY button for over 10 seconds With a beep sound the unit is set to the forced cooling mode In approximately three minutes it is forced to start in cooling mode Determine that cool air comes out...

Page 18: ...eck if there is any clogging or drain water is polluted Maintenance List Part Unit Check visual auditory Maintenance Heat exchanger Indoor outdoor Dust dirt clogging scratches Wash the heat exchanger when it is clogged Fan motor Indoor outdoor Sound Take appropriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace...

Page 19: ...log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to s...

Page 20: ...tion circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master r...

Page 21: ...ALT Ps sensor error I F F24 F24 ALT Pd sensor error I F F29 SIM Indoor unit other error Indoor unit F31 F31 SIM Indoor unit EEPROM error I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04...

Page 22: ... unit L31 Extended I C error I F P01 ALT Indoor fan motor error Indoor unit P03 P03 ALT Discharge temp TD1 error I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation IPDU P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC volta...

Page 23: ...06 Comp 2 Comp 3 07 Comp 1 Comp 2 Comp 3 08 Fan 09 Comp 1 Fan 0A Comp 2 Fan 0B Comp 1 Comp 2 Fan 0C Comp 3 Fan 0D Comp 1 Comp 3 Fan 0E Comp 2 Comp 3 Fan 0F Comp 1 Comp 2 Comp 3 Fan Error detected by TCC LINK central control device Check code Wireless remote controller Check code name Judging device Wired remote controller display Outdoor unit 7 segment display Sensor block display of receiving uni...

Page 24: ...ited Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMC AP0157HP E MMC AP0187HP E MMC AP0247HP E MMC AP0277HP E MMC AP0367HP E MMC AP0487HP E MMC AP0567HP E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies w...

Page 25: ... Min volume of the indoor unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device Important 2 When there is an effective opening with the adjacent room for venti...

Page 26: ...1114652499 ...

Reviews: