193
Check code name
[P12] / [11]
(d07 / AI-NET)
Check code name
Indoor fan motor error
Cause of operation
1. Cabling error of fan motor connector
2. Fan motor error
3. Indoor P.C. board error
Turn off power supply.
Correct connector connection.
Check indoor P.C. board (MCC-1402).
Failure
Replace
Is resistance value at motor side of
fan motor connector CN334 on indoor P.C. board
(MCC-1402) correct? *2
Is resistance value between each phase
at motor side of fan motor connector CN333 on
indoor P.C. board (MCC-1402) correct? *1
Is there connection error or
disconnection on connector CN333, CN334
of indoor P.C. board (MCC-1402)?
Is output of indoor fan motor position
detective signal correct? *3
Does fan turn without trouble
when turning it with hands?
Remove connectors CN333 and CN334
on indoor P.C. board (MCC-1402).
*2
Check resistance value of fan motor position detective circuit.
• Is not winding 1 (Yellow lead) to 4 (Pink lead) opened/shorted?
Resistance should be 5 to 20k
*3
Check fan motor position detective signal.
• Measure voltage with tester between CN334 1 and 5 on indoor P.C. board (MCC-1402)
under condition of CN333 and CN334 installed and power-ON.
Turn fan slowly with hands so that pin voltage
fluctuates
between 0 and 5V.
• Between 4 and 5: 5V
*1
• Is not winding 1 (Red lead) to 3 (White lead), 3 (White lead) to 5 (Black lead),
5 (Black lead) to 1 (Red lead) opened/shorted?
Resistance value should satisfy the follows.
[4-way Air Discharge Cassette type]
MMU-AP0091H, AP0301
Approx. 70 to 100
MMU-AP0361H, AP0561
Approx. 35 to 50
[Concealed Duct Standard type]
15 to 35
• Is not grounded between cabinet and 1, 3, 5?
Should be
10 or more
* Detectable in model with DC fan motor
(4-way Air Discharge Cassette, or Concealed Duct Standard type)
Replace indoor fan motor.
Replace indoor fan motor.
Replace indoor fan motor.
Replace indoor fan motor.
CN333
CN334
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Summary of Contents for MMC-AP0151H
Page 270: ......