209
5. Data display of indoor unit information (Displayed on the header unit only)
SW01
4
5
6
7
8
9
10
11
12
13
SW02
1 to 16
SW03
1 to 3
Display contents
Receiving status of
B
Receiving time: [… … 1], Not received: [… … …]
indoor BUS communication
Indoor check code
B
No check code: [– – –]
Indoor capacity
B
0. 2, 0. 5, 0. 8, … 1, 1. 2, 1. 7, … 2, 2. 5, … 3, 3. 2, … 4, … 5,
(HP) horse power
… 6, … 8, 1 0, 1 6, 2 0
Indoor request command
B
Data is displayed with Hexadecimal notation [… … 0 to … … F] : Heating
(S code)
Indoor PMV opening data
B
Data is displayed with Hexadecimal notation
Indoor TA sensor data
B
Data is displayed with Hexadecimal notation
Indoor TF sensor data
B
Data is displayed with Hexadecimal notation
Indoor TCJ sensor data
B
Data is displayed with Hexadecimal notation
Indoor TC1 sensor data
B
Data is displayed with Hexadecimal notation
Indoor TC2 sensor data
B
Data is displayed with Hexadecimal notation
NOTE) Indoor address No. is chosen by changing SW02 and SW03.
SW03
1
2
3
SW02
1 to 16
1 to 16
1 to 16
Indoor address
SW02 setup number
SW02 setup 16
SW02 setup 32
7-segment display A
[01] to [16]
[17] to [32]
[33] to [48]
6. Outdoor EEPROM write-in error code display (Displayed on the header unit only)
∗
The latest error code written in EEPROM of each outdoor unit is displayed.
(It is used when confirming the error code after power supply has been reset.)
Set SW01 to 03 as shown in the following table, and the push SW04 for 5 seconds or more to display an
error code.
SW01
1
SW02
1
2
3
4
SW03
16
Display contents
The latest error code of the header unit 1 (U1)
The latest error code of the follower unit 1 (U2)
The latest error code of the follower unit 2 (U3)
The latest error code of the follower unit 3 (U4)
7-segment display
A
B
E. r
1. – –
E. r
2. – –
E. r
3. – –
E. r
4. – –