172
Check code name
[H03] / [17]
(d07 / AI-NET)
Check code name
Current detective circuit system error
Cause of operation
1. Cabling or connector connection error on
IPDU P.C. board
2. IPDU P.C. board error
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
YES
NO
Check IPDU P.C. board.
Correct connector connection or cabling.
Wiring or connector connection
on IPDU P.C. board normal?
Summary of Contents for MMC-AP0151H