<Other cautions>
1. Cooling operation in low ambient temperature
1) When low pressure is lowered, the freeze prevention control by the indoor unit TC sensor may decrease
the frequency.
2) When low pressure is lowered, the cooling capacity control may decrease the frequency.
3) When discharge temp. sensor value lowers below 60°C, the frequency may be increased over the
receive command from the indoor unit.
2. PMV (Pulse Motor Valve) for outdoor unit
1) When the power is turned on, a tap sound to initialize PMV is heard. If this sound is not heard, PMV
operation error is considered. However, this sound may not be heard at a place where outside sound
takes precidence.
2) Do not remove the driving part (Head part) of PMV during operation. It may cause error in opening.
3) When transporting (replacing) the set, never keep the driving part removed. The valve is closed, and the
valve is damaged by sealed liquid compression.
4) When removing the driving part and attaching it again, push in it securely until a “click” sound can be
heard. Then, turn off the power once, and turn on the power again.
<Oil equation control schematic diagram>
FM
TO
TS1
Liquid
tank
4-Way valve
Accumulator
TK2
TK4
TK1
SV3E
SV41
SV42
SV3D
SV3A
TK3
SV3C
Oil tank
Header outdoor unit
(MMY-MAP1201HT)
Follower outdoor unit
(MMY-MAP1201HT)
TE1
SV5
SV3B
Ps sensor
SV2
TL
PMV1
PMV2
Compressor
1
Compressor
2
TD1
HP
HP
TD2
Pd sensor
FM
TO
TS1
Liquid
tank
4-Way valve
Accumulator
TK2
TK4
TK1
SV3E
SV41
SV42
SV3D
Oil
separator
SV3A
TK3
SV3C
Oil tank
OS
TE1
SV5
SV3B
Ps sensor
SV2
TL
PMV1
PMV2
Compressor
1
Compressor
2
TD1
HP
HP
TD2
Pd sensor
Gas pipe
Liquid pipe
Balance pipe
Unit to
send oil
Unit to
received oil
ON
ON
ON
Summary of Contents for MMC-AP0151H
Page 270: ......