147
Error detected by TCC-LINK central control device
Check code
Display on
central control
device
C05
C06
C12
P30
Outdoor 7-segment display
Sub-code
—
—
—
(L20 is displayed.)
AI-NET
central control
remote controller
—
—
—
Detected
position
TCC-LINK
General-
purpose device
I/F
TCC-LINK
Check code name
TCC-LINK central control
device transmission error
TCC-LINK central control
device receiving error
Interface batch alarm of
general-purpose control
devices
Follower unit error of
group control
Duplicated central
control address
Status
Operation
continued.
Operation
continued.
Operation
continued.
Operation
continued.
Operation
continued.
Error detection condition
Signal is not transmit from
central control device.
Signal is not received from
central control device.
Error was input in general-
purpose control device
control interface.
An error occurred in follower
unit of the group control.
([P30] is displayed only on
the central control remote
controller.)
Central control addresses
were duplicated.
Check item (position)
• Check central control device error.
• Check communication line error of central control device.
• Check setup of end terminal resistance.
• Check central control device error.
• Check communication line error of central control device.
• Check setup of end terminal resistance.
• Check the power of connecting destination connected device.
• Check P.C. board error of the connected device.
• Check error input.
• Check the check code of the unit with alarm.
• Check the address setup.
Differs according to error contents of the with
alarm
Error detected by AI-NET central control device
Check code
Main
remote
controller
—
—
—
Outdoor 7-segment display
Check code
Sub-code
—
—
—
—
—
—
AI-NET
central control
remote controller
97
99
b7
Detected
position
AI-NET
AI-NET
AI-NET
Check code name
AI-NET communication
system error
Duplicated network
adaptors
Error in indoor group
Status
Operation
continued.
Operation
continued.
Operation
continued.
Error detection condition
E07/L07/L03/L08 was
detected when other indoor
unit in the group was
defective.
Multiple network adaptors
were connected to
communication line of
remote controller.
(Detected at central
controller side)
Error of follower unit in the
group
Check item (position)
• Check multiple network adaptors.
• Check wire and miscabling of remote controller: Only one network
adaptor can be connected to communication line of remote
controller.
• Check communication line, miscabling, and power of indoor unit.
• Check communication. (X, Y terminals)
• Check network adaptor P.C. board.
• Check the central controller (Central control remote controller, etc.)
• Check follower unit in the group.
∗
These errors are concerned to communication of remote controllers (A, B) and central system [AI-NET X, Y], and the main remote controller displays [E01], [E02], [E03], [E09], or
[E18] in some cases and displays none in other cases according to the contents.
Summary of Contents for MMC-AP0151H