92
8-3. Check at Main Power-ON
After turning on the main power of the indoor units and outdoor unit in the refrigerant line to be executed with a
test operation, check the following items in each outdoor and indoor unit.
(After turning on the main power, be sure to check in order of indoor unit
→
→
→
→
→
outdoor unit.)
<Check on outdoor unit>
1. Check that all the rotary switches, SW01, SW02, and SW03 on the interface P.C. board of the header unit are
set up to “1”.
2. If other error code is displayed on 7-segment [B], remove the cause of trouble referring to
“9. Troubleshooting”.
3. Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the header unit.
(L08: Indoor address unset up)
(If the address setup operation has already finished in service time, etc, the above check code is not dis-
played, and only [U1] is displayed on 7-segment display [A].)
<Check on indoor unit>
1. Display check on remote controller (In case of wired remote controller)
Check that a frame as shown in the following left figure is displayed on LC display section of the remote
controller.
If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally
turned on. Therefore check the following items.
• Check power supply of indoor unit.
• Check cabling between indoor unit and remote controller.
• Check whether there is cutoff of cable around the indoor control P.C. board or not, and check connection
failure of connectors.
• Check failure of transformer for the indoor microcomputer.
• Check indoor control P.C. board failure.
UNIT
SET
CL
UNIT
SET
CL
Normal status
(Power and operation stop)
Abnormal status
(Power is not normally turned on.)
Interface P.C. board
7-segment display [A]
SW01
SW02
SW03
7-segment display [B]