9-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit
(7-Segment Display of Interface)
Check code
Main
remote
controller
E01
E02
E03
E04
E06
—
E08
E09
E10
Outdoor 7-segment display
Check code
Sub-code
—
—
—
—
—
—
—
—
E06
No. of indoor units which
received signal normally
E07
—
E08
Duplicated indoor
addresses
—
—
—
—
AI-NET
central control
remote controller
—
—
97
4
4
—
96
99
CF
Detected
position
Remote
controller
Remote
controller
Indoor
unit
Indoor
unit
I/F
I/F
Indoor
I/F
Remote
controller
Indoor
unit
Check code name
Communication error between
indoor and remote controller
(Detected at remote controller side)
Remote controller sending error
Communication error between
indoor and remote controller
(Detected at indoor side)
Indoor/outdoor communication
circuit error
(Detected at indoor side)
Decreased number of indoor units
Indoor/outdoor communication
circuit error
(Detected at outdoor side)
Duplicated indoor addresses
Duplicated master remote
controllers
Communication error between
indoor P.C. board assembly
Status
Corresponding
unit only stops.
Corresponding
unit only stops.
Corresponding
unit only stops.
Corresponding
unit only stops.
All stop
All stop
All stop
Corresponding
unit only stops.
Corresponding
unit only stops.
Error detection condition
Communication interrupted
between indoor P.C. board and
remote controller.
Signal could not be sent from
remote controller to indoor unit.
No communication from remote
controller (including wireless) and
communication adaptor.
Indoor unit does not receive
communication from outdoor unit.
When signal is not sent for a
certain period from the indoor
unit which has been used to
send signals, [E06] is normally
displayed.
Transmission from outdoor to
indoor cannot continue for 30
seconds.
Multiple indoor unit address
setup are duplicated.
In 2-remote controller control
(including wireless), both are
setup as master
(Header indoor unit stops and
other indoor unit is operating.)
There is any trouble in power
line.
Check item (position)
• Check remote controller inter-unit cable (A/B).
• Check disconnection, connector contact error.
• Check indoor power supply.
• Check indoor P.C. board error.
• Check remote controller address setup.
(When two remote controllers operate)
• Check remote controller P.C. board.
• Check the communication wire of remote
controller: Exchange remote controller.
• Check remote controller and communication
adaptor wiring.
• Check power-ON order of indoor/outdoor.
• Check indoor address setup.
• Check inter-unit cabling between indoor and
outdoor.
• Check outdoor end terminal resistance setup
(SW30-2).
• Check the power supply of indoor unit.
(Power-ON)
• Check connection of communication line
between indoor and outdoor.
• Check connector connection for communication
in indoor P.C. board.
• Check connector connection for communication
in outdoor P.C. board.
• Check indoor P.C. board failure.
• Check outdoor P.C. board (I/F) failure.
• Check outdoor end terminal resistance setup
(SW30-2).
• Check the communication connection between
indoor and outdoor.
• Check indoor address.
• Check the change of remote controller
connection (Group / individual) after setup of
indoor address.
• Check remote controller setup.
• Check remote controller P.C. board.
• Indoor P.C. board failure