250
⎯
6 F 2 S 0 8 2 8
List of Information
IEC103 Configurator Default setting
INF
Description
Contents
GI
Type
COT
FUN
DPI
ID
Signal No.
OFF ON
Standard Information numbers in monitor direction
System Function
0
End of General Interrogation
Transmission completion of GI items.
--
8
10
255
--
--
--
0
Time Synchronization
Time Synchronization ACK.
--
6
8
255
--
--
--
2
Reset FCB
Reset FCB(toggle bit) ACK
--
5
3
192
--
--
--
3
Reset CU
Reset CU ACK
--
5
4
192
--
--
--
4
Start/Restart
Relay start/restart
--
5
5
192
--
--
--
5
Power On
Relay power on.
Not supported
--
--
--
Status Indications
16 Auto-recloser active
If it is possible to use auto-recloser, this item is set
active, if impossible, inactive.
Not supported
17 Teleprotection active
If protection using telecommunication is available,
this item is set to active. If not, set to inactive.
GI
1
1, 9, 12
192
722
1
2
18 Protection active
If the protection is available, this item is set to
active. If not, set to inactive.
GI
1
1, 9, 12
192
723
1
2
19 LED reset
Reset of latched LEDs
--
1
1, 11, 12
192
1418
--
2
20 Monitor direction blocked
Block the 103 transmission from a relay to control
system. IECBLK: "Blocked" settimg.
GI
1
9, 11
192
1040
1
2
21 Test mode
Transmission of testmode situation froma relay to
control system. IECTST "ON" setting.
GI
1
9, 11
192
1039
1
2
22 Local parameter Setting
When a setting change has done at the local, the
event is sent to control system.
Not supported
23 Characteristic1
Setting group 1 active
GI
1
1, 9, 11, 12
192
1024
1
2
24 Characteristic2
Setting group 2 active
GI
1
1, 9, 11, 12
192
125
1
2
25 Characteristic3
Setting group 3 active
GI
1
1, 9, 11, 12
192
1026
1
2
26 Characteristic4
Setting group 4 active
GI
1
1, 9, 11, 12
192
1027
1
2
27 Auxiliary input1
Binary input 1
No set
28 Auxiliary input2
Binary input 2
No set
29 Auxiliary input3
Binary input 3
No set
30 Auxiliary input4
Binary input 4
No set
Supervision Indications
32 Measurand supervision I
Zero sequence current supervision
GI
1
1, 9
192
1356
1
2
33 Measurand supervision V
Zero sequence voltage supervision
Not supported
35 Phase sequence supervision
Negative sequence voltage supevision
Not supported
36 Trip circuit supervision
Output circuit supervision
GI
1
1, 9
192
1359
1
2
37 I>>backup operation
Not supported
38 VT fuse failure
VT failure
Not supported
39 Teleprotection disturbed
CF(Communication system Fail) supervision
GI
1
1, 9
192
439
1
2
46 Group warning
Only alarming
GI
1
1, 9
192
1346
1
2
47 Group alarm
Trip blocking and alarming
GI
1
1, 9
192
1343
1
2
Earth Fault Indications
48 Earth Fault L1
A phase earth fault
No set
49 Earth Fault L2
B phase earth fault
No set
50 Earth Fault L3
C phase earth fault
No set
51 Earth Fault Fwd
Earth fault forward
Not supported
52 Earth Fault Rev
Earth fault reverse
Not supported
Summary of Contents for GRL150-100 Series
Page 149: ... 148 6 F 2 S 0 8 2 8 ...
Page 154: ... 153 6 F 2 S 0 8 2 8 Appendix B Signal List ...
Page 180: ... 179 6 F 2 S 0 8 2 8 Appendix C Binary Output Default Setting List ...
Page 182: ... 181 6 F 2 S 0 8 2 8 Appendix D Details of Relay Menu ...
Page 195: ... 194 6 F 2 S 0 8 2 8 ...
Page 196: ... 195 6 F 2 S 0 8 2 8 Appendix E Case Outline ...
Page 199: ... 198 6 F 2 S 0 8 2 8 ...
Page 200: ... 199 6 F 2 S 0 8 2 8 Appendix F Typical External Connections ...
Page 223: ... 222 6 F 2 S 0 8 2 8 ...
Page 228: ... 227 6 F 2 S 0 8 2 8 Appendix I Return Repair Form ...
Page 232: ... 231 6 F 2 S 0 8 2 8 Appendix J Technical Data ...
Page 238: ... 237 6 F 2 S 0 8 2 8 Appendix K Symbols Used in Scheme Logic ...
Page 241: ... 240 6 F 2 S 0 8 2 8 ...
Page 242: ... 241 6 F 2 S 0 8 2 8 Appendix L Inverse Time Characteristics ...
Page 248: ... 247 6 F 2 S 0 8 2 8 Appendix M IEC60870 5 103 Interoperability ...
Page 260: ... 259 6 F 2 S 0 8 2 8 Appendix N Resistor Box Option ...
Page 263: ... 262 6 F 2 S 0 8 2 8 ...
Page 264: ... 263 6 F 2 S 0 8 2 8 Appendix O Ordering ...
Page 267: ......