133
⎯
6 F 2 S 0 8 2 8
6.5.1.1 Phase current differential element DIF
The phase current differential element is checked for the following items.
Operating current value
Percentage restraining characteristic
The top two items are tested locally or under an end-to-end setup of each terminal relay.
The last item is tested only under an end-to-end setup of each terminal relay.
Operating current value
Figure 6.5.1.1 shows the circuit to test the element locally.
GRL150
Single-phase
current
source
A
TB1 -1
-2
RX
TX
Ia
Monitoring
jack
A
0V
DC
voltmeter
TB2 -A9
-B9
E
DC
power
supply
+
−
Figure 6.5.1.1 Testing Phase Current Differential Element
The output signal numbers of the DIF element are as follows.
Element Signal
number
DIF-A 48
DIF-B 49
DIF-C 50
•
Set the [L.test] to “1” (= On) on the “Switch” screen of the “Test” sub-menu. See Section 4.2.7.
•
Select the "Logic circuit" on the "Test" sub-menu screen to display the "Logic circuit" screen.
•
Enter a signal number 48 for Term A line to observe the DIF-A operation at monitoring jack A
and press the ENTER key.
•
Apply a test current and change the magnitude of the current applied and measure the value at
which the element operates.
•
Check that the measured value is within 7% of the setting DIFI1.
Summary of Contents for GRL150-100 Series
Page 149: ... 148 6 F 2 S 0 8 2 8 ...
Page 154: ... 153 6 F 2 S 0 8 2 8 Appendix B Signal List ...
Page 180: ... 179 6 F 2 S 0 8 2 8 Appendix C Binary Output Default Setting List ...
Page 182: ... 181 6 F 2 S 0 8 2 8 Appendix D Details of Relay Menu ...
Page 195: ... 194 6 F 2 S 0 8 2 8 ...
Page 196: ... 195 6 F 2 S 0 8 2 8 Appendix E Case Outline ...
Page 199: ... 198 6 F 2 S 0 8 2 8 ...
Page 200: ... 199 6 F 2 S 0 8 2 8 Appendix F Typical External Connections ...
Page 223: ... 222 6 F 2 S 0 8 2 8 ...
Page 228: ... 227 6 F 2 S 0 8 2 8 Appendix I Return Repair Form ...
Page 232: ... 231 6 F 2 S 0 8 2 8 Appendix J Technical Data ...
Page 238: ... 237 6 F 2 S 0 8 2 8 Appendix K Symbols Used in Scheme Logic ...
Page 241: ... 240 6 F 2 S 0 8 2 8 ...
Page 242: ... 241 6 F 2 S 0 8 2 8 Appendix L Inverse Time Characteristics ...
Page 248: ... 247 6 F 2 S 0 8 2 8 Appendix M IEC60870 5 103 Interoperability ...
Page 260: ... 259 6 F 2 S 0 8 2 8 Appendix N Resistor Box Option ...
Page 263: ... 262 6 F 2 S 0 8 2 8 ...
Page 264: ... 263 6 F 2 S 0 8 2 8 Appendix O Ordering ...
Page 267: ......