6.5.1.2 Overcurrent and undercurrent element OC1 to OC4, OC5, UC1, UC2 and CBF and Earth
fault element EF1 to EF4 and SEF1 to SEF4
The overcurrent element is checked on the operating current value and operating time for IDMT
curve.
Operating current check
Figure 6.5.1.4 shows a testing circuit. The operating current value is checked by increasing or
decreasing the magnitude of the current applied.
Single-phase
current
source
TB1
TB2
-(*)
-A9
-B9
GRL150
DC
power
supply
+
−
+
−
A
-(*)
E
(
∗
): Connect the terminal number corresponding to the testing element. Refer to Table 3.2.1.
DC
voltmeter
Monitoring
jack
A
0V
+
0V
Figure 6.5.1.4 Operating Current Value Test
The output signal of testing element is assigned to the monitoring jack A.
The output signal numbers of the elements are as follows:
Element
Signal No.
Element
Signal No.
Element
Signal No. Element
Signal No.
OC1-A
80
EF1
112
SEF1
116
UC1-A
176
OC2-A
84 EF2
113 SEF2
117 UC2-A 180
OC3-A
88 EF3
114 SEF3
118 CBF-A 124
OC4-A
92 EF4
115 SEF4
119 OC5-A 64
•
Enter the signal number to observe the operation at the LED as shown in Section 6.5.1 and
press the ENTER key.
•
Apply a test current and change the magnitude of the current applied and measure the value
at which the element operates.
Check that the measured value is within 5% of the setting value.
Summary of Contents for GRL150-100 Series
Page 149: ... 148 6 F 2 S 0 8 2 8 ...
Page 154: ... 153 6 F 2 S 0 8 2 8 Appendix B Signal List ...
Page 180: ... 179 6 F 2 S 0 8 2 8 Appendix C Binary Output Default Setting List ...
Page 182: ... 181 6 F 2 S 0 8 2 8 Appendix D Details of Relay Menu ...
Page 195: ... 194 6 F 2 S 0 8 2 8 ...
Page 196: ... 195 6 F 2 S 0 8 2 8 Appendix E Case Outline ...
Page 199: ... 198 6 F 2 S 0 8 2 8 ...
Page 200: ... 199 6 F 2 S 0 8 2 8 Appendix F Typical External Connections ...
Page 223: ... 222 6 F 2 S 0 8 2 8 ...
Page 228: ... 227 6 F 2 S 0 8 2 8 Appendix I Return Repair Form ...
Page 232: ... 231 6 F 2 S 0 8 2 8 Appendix J Technical Data ...
Page 238: ... 237 6 F 2 S 0 8 2 8 Appendix K Symbols Used in Scheme Logic ...
Page 241: ... 240 6 F 2 S 0 8 2 8 ...
Page 242: ... 241 6 F 2 S 0 8 2 8 Appendix L Inverse Time Characteristics ...
Page 248: ... 247 6 F 2 S 0 8 2 8 Appendix M IEC60870 5 103 Interoperability ...
Page 260: ... 259 6 F 2 S 0 8 2 8 Appendix N Resistor Box Option ...
Page 263: ... 262 6 F 2 S 0 8 2 8 ...
Page 264: ... 263 6 F 2 S 0 8 2 8 Appendix O Ordering ...
Page 267: ......