– 97 –
7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
Function code settings
Function code setting
Function code
setting address
Default
Range
Unit
Unit
Note
Hydro
unit
Remote
controller
1. Setting
temperature range
01. Upper-limit temperature for
heating Zone 1
1A
55
37 to 55
°C
1
02. Lower-limit temperature for
heating Zone 1
1B
20
20 to 37
°C
1
03. Upper-limit temperature for
heating Zone 2
1C
55
37 to 55
°C
1
04. Lower-limit temperature for
heating Zone 2
1D
20
20 to 37
°C
1
05. Upper-limit temperature for
cooling
18
25
18 to 30
°C
1
06. Lower-limit temperature for
cooling
19
10
10 to 18
°C
1
07. Upper-limit temperature for
hot water
1E
75
60 to 80
°C
1
08. Lower-limit temperature for
hot water
1F
40
40 to 60
°C
1
2. Hot water
operation
01. Heat pump start temperature
20
38
20 to 45
°C
1
02. Heat pump stop temperature
21
45
40 to 50
°C
1
3. Hot water
temperature
compensation
01. Temperature compensation
start outside air temperature
24
0
-20 to 10
°C
1
02. Compensation temperature
25
3
0 to 15
Degree
1
4. Hot Water Boost
01. Operation time x 10 min
08
6
3 to 18
Minute
1 (x10)
02. Setting temperature
09
75
40 to 80
°C
1
5. Anti -bacteria
01. Setting temperature
0A
75
70 to 80
°C
1
02. Operation cycle
0D
7
1 to 10
Day
1
03. Start time
0C
22
0 to 23
Hour
1
04. Operation time
0B
30
0 to 60
Minute
1
6. Priority mode
01. Hot water and heating
switching temperature
22
0
-20 to 20
°C
1
02. Boiler and heat pump
switching temperature
23
-10
-20 to 20
°C
1
7. Heating Auto
setting
01. Outside temperature T1
29
-10
-15 to 0
°C
1
02. Outside temperature T3
2B
10
0 to 15
°C
1
03. Setting
temperature A at
-20°C
When A
≥
B
≥
C
≥
D
≥
E
2C
40
20 to 55
°C
1
04. Setting
temperature B at T1°C
2D
35
20 to 55
°C
1
05. Setting
temperature C at T2°C
2E
30
20 to 55
°C
1
06. Setting
temperature D at T3°C
2F
25
20 to 55
°C
1
07. Setting
temperature E at
+20°C
30
20
20 to 55
°C
1
08. Ratio of Zone 2 in Zone 1
Auto mode
31
80
0 to 100
%
10
09. Temperature shift of entire
AUTO curve
27
0
-5 to 5
Degree
1
35-EN
Summary of Contents for ESTIA HWS-1102H-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 10: ...9 3 SYSTEM SPECIFICATION ...
Page 12: ...11 4 HYDRO UNIT ...
Page 44: ...43 5 OUTDOOR UNIT ...
Page 57: ...56 6 HOT WATER CYLINDER ...
Page 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 131: ...129 9 OWNER S MANUAL ...
Page 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...