– 123 –
8. OUTDOOR UNIT INSTALLATION MANUAL
Engineering Data book
How to wire
1. Connect the connecting wire to the terminal as
identified with their respective numbers on the
terminal block of hydro and outdoor unit.
H07 RN-F or 60245 IEC 66 (1.5 mm
2
or more)
2. When connecting the connecting wire to the outdoor
unit terminal, prevent water coming in the outdoor
unit.
3. Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.
4. For inter connecting wire, do not use a wire jointed
to another on the way.
Use wires long enough to cover the entire length.
Stripping length power cord and connecting
wire
CAUTION
• The installation fuse must be used for the power
supply line of this outdoor unit.
• Incorrect/incomplete wiring might cause an electrical
fire or smoke.
• Prepare the exclusive power supply for the Air to
Water Heat Pump.
• This product can be connected to the mains.
Connection to the fixed wiring :
A switch which disconnects all poles and has a
contact separation of at least 3 mm must be
incorporated in the fixed wiring.
L
N
1
2
3
Power supply
terminal block
Power supply
wire
Earth screw
To Hydro unit
terminal block
Earth screw
Connecting wire
Pipe valve fixing
plate
(mm)
10
10
L N
40
10
50
50
10
30
1 2 3
Power supply
wire
Earth line
Earth line
Connecting wire
17-EN
Summary of Contents for ESTIA HWS-1102H-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 10: ...9 3 SYSTEM SPECIFICATION ...
Page 12: ...11 4 HYDRO UNIT ...
Page 44: ...43 5 OUTDOOR UNIT ...
Page 57: ...56 6 HOT WATER CYLINDER ...
Page 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 131: ...129 9 OWNER S MANUAL ...
Page 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...