3.SYSTEM SPECIFICATION
Engineering Data book
10
3
* Rated condition capacity and power input are the data at rated compressor operating frequency.
* Power input does not include water pump power.
* Capacity and power input are measured in accordance with EN14511.
Outdoor unit
HWS-802H-E
HWS-1102H-E
HWS-1402H-E
Hydro unit
HWS-802XWH**-E
HWS-1402XWH**-E
Rated heating
condition
TO (DB/WB)=7/6°C
LWT=35°C dT=5deg
Capacity
kW
8.0
11.2
14.0
Power input
kW
1.96
2.4
3.15
COP
W/W
4.08
4.66
4.45
Rated water flow
/min
22.9
32.1
40.1
Rated heating
condition
TO (DB/WB)=7/6°C
LWT=45°C dT=5deg
Capacity
kW
8.0
11.2
14.0
Power input
kW
2.40
2.95
3.95
COP
W/W
3.33
3.80
3.54
Rated water flow
/min
22.9
32.1
40.1
Rated cooling
condition
TO=35°C
LWT=7°C dT=5deg
Capacity
kW
6.0
10.0
11.0
Power input
kW
2.13
3.52
4.08
EER
W/W
2.82
2.84
2.69
Rated water flow rate
/min
17.2
28.7
31.5
Rated cooling
condition
TO=35°C
LWT=18°C dT=5deg
Capacity
kW
6.0
10
11
Power input
kW
1.42
2.35
2.65
EER
W/W
4.23
4.26
4.15
Rated water flow
/min
17.2
28.7
31.5
Power supply
1~ 230V 50Hz
Maximum current
A
20.8
22.8
22.8
TO
:
Outdoor temperature (°C)
LWT
:
Leaving water temperature (°C)
dT
:
Delta temperature (deg)
Leaving water temperature - return water temperature (Heating)
Return water temperature - leaving water temperature (Cooling)
Summary of Contents for ESTIA HWS-1102H-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 10: ...9 3 SYSTEM SPECIFICATION ...
Page 12: ...11 4 HYDRO UNIT ...
Page 44: ...43 5 OUTDOOR UNIT ...
Page 57: ...56 6 HOT WATER CYLINDER ...
Page 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 131: ...129 9 OWNER S MANUAL ...
Page 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...