4.HYDRO UNIT
Engineering Data book
34
4
Cooling capacity and power input
* Cooling capacity and power input are include are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
12.78
13.64
14.99
16.03
16.98
27
11.60
12.38
13.61
14.55
15.42
30
11.03
11.77
12.94
13.83
14.66
35
10.00
10.67
11.73
12.54
13.29
40
8.96
9.56
10.51
11.24
11.91
43
6.89
7.35
8.08
8.64
9.16
Power input (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
2.64
2.70
2.74
2.77
2.78
27
3.04
3.11
3.16
3.18
3.20
30
3.23
3.30
3.35
3.38
3.40
35
3.52
3.59
3.65
3.68
3.70
40
3.82
3.84
3.86
3.88
3.91
43
3.28
3.28
3.28
3.29
3.29
EER
LWT (°C)
7
10
13
15
18
TO
(°C)
20
4.83
5.05
5.47
5.80
6.11
27
3.81
3.98
4.31
4.57
4.81
30
3.41
3.57
3.86
4.09
4.31
35
2.84
2.97
3.21
3.41
3.59
40
2.34
2.49
2.72
2.90
3.04
43
2.10
2.24
2.46
2.62
2.78
TO
:
Outdoor temperature (DB°C)
LWT
:
Leaving water temperature (°C)
Summary of Contents for ESTIA HWS-1102H-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 10: ...9 3 SYSTEM SPECIFICATION ...
Page 12: ...11 4 HYDRO UNIT ...
Page 44: ...43 5 OUTDOOR UNIT ...
Page 57: ...56 6 HOT WATER CYLINDER ...
Page 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 131: ...129 9 OWNER S MANUAL ...
Page 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...