– 142 –
9. OWNER’S MANUAL
Engineering Data book
9
General Specifications
Outdoor unit
HWS-802H-E
HWS-1102H-E
HWS-1402H-E
Type
Inverter
Function
Heating & Cooling
Heating
Capacity
(kW)
8.0
11.2
14.0
Input
(kW)
1.96
2.40
3.15
COP
4.08
4.66
4.45
Cooling
Capacity
(kW)
6.0
10.0
11.0
Input
(kW)
2.13
3.52
4.08
EER
2.82
2.84
2.69
Power supply
230 V ~
Refrigerant
R410 A
Dimension
HxWxD
(mm)
890 x 900 x 320
1,340 x 900 x 320
Hydro Unit
HWS-
802XWHM3-E
HWS-
802XWHT6-E
HWS-
1402XWHM3-E
HWS-
1402XWHT6-E
HWS-
1402XWHT9-E
Back up heater capacity
3 kW
6 kW
3 kW
6 kW
9 kW
Power supply
for backup heater
230 V ~
400 V 3N ~
230 V ~
400 V 3N ~
400 V 3N ~
for hot water cylinder
heater (option)
230 V ~
Leaving water
temperature
Heating
(°C)
20 to 55
Cooling
(°C)
10 to 25
For use with
HWS-802H-E
HWS-1102H-E/HWS-1402H-E
Dimension
HxWxD
(mm)
925 x 525 x 355
Hot water cylinder (option)
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
Water volume
litres
150
210
300
Max water temperature
(°C)
75
Electric heater
(kW)
2.75
Height
(mm)
1,090
1,474
2,040
Diameter
(mm)
550
Material
Stainless steel
12-EN
Summary of Contents for ESTIA HWS-1102H-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 10: ...9 3 SYSTEM SPECIFICATION ...
Page 12: ...11 4 HYDRO UNIT ...
Page 44: ...43 5 OUTDOOR UNIT ...
Page 57: ...56 6 HOT WATER CYLINDER ...
Page 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 131: ...129 9 OWNER S MANUAL ...
Page 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...