4.HYDRO UNIT
Engineering Data book
25
4-5. Capacity Tables
▼
Outdoor unit
HWS-802H-E
Hydro unit
HWS-802XWH**-E
Rated heating capacity and power input
* Rated heating capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
Rated condition 1
TO (DB/WB)=7/6°C
LWT=35°C
dT=5deg
Capacity
kW
8.0
Power input
kW
1.96
COP
W/W
4.08
Rated water flow rate
/min
22.9
Rated condition 2
TO (DB/WB)=7/6°C
LWT=45°C
dT=5deg
Capacity
kW
8.0
Power input
kW
2.40
COP
W/W
3.33
Rated water flow rate
/min
22.9
TO
:
Outdoor temperature (DB°C) RH85%
LWT
:
Leaving water temperature (°C)
dT
:
Delta temperature (deg)
Leaving water temperature - return water temperature