Cooling capacity and power input
* Cooling capacity and power input are include are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
13.95
15.48
16.82
17.53
18.34
27
12.60
13.98
15.19
15.83
16.56
30
12.01
13.33
14.49
15.10
15.80
35
11.00
12.21
13.27
13.83
14.47
40
8.83
9.80
10.65
11.10
11.62
43
6.81
7.56
8.21
8.56
8.95
Power input (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
3.14
3.21
3.26
3.27
3.30
27
3.57
3.64
3.70
3.72
3.76
30
3.77
3.85
3.91
3.92
3.97
35
4.08
4.17
4.23
4.25
4.29
40
3.84
3.85
3.85
3.87
3.88
43
3.25
3.23
3.23
3.22
3.22
EER
LWT (°C)
7
10
13
15
18
TO
(°C)
20
4.44
4.83
5.16
5.36
5.55
27
3.53
3.84
4.10
4.26
4.41
30
3.19
3.46
3.71
3.85
3.98
35
2.70
2.93
3.14
3.26
3.37
40
2.30
2.55
2.76
2.87
3.00
43
2.10
2.34
2.54
2.65
2.78
TO
:
Outdoor temperature (DB°C)
LWT
:
Leaving water temperature (°C)
Summary of Contents for ESTIA HWS-1102H-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 10: ...9 3 SYSTEM SPECIFICATION ...
Page 12: ...11 4 HYDRO UNIT ...
Page 44: ...43 5 OUTDOOR UNIT ...
Page 57: ...56 6 HOT WATER CYLINDER ...
Page 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 131: ...129 9 OWNER S MANUAL ...
Page 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...