4.HYDRO UNIT
Engineering Data book
29
Cooling capacity and power input
* Cooling capacity and power input are the data at rated compressor operating frequency of rated condition 1
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
7.36
8.05
8.81
9.25
10.03
27
6.76
7.39
8.09
8.49
9.21
30
6.46
7.06
7.73
8.12
8.80
35
6.00
6.56
7.18
7.54
8.18
40
5.50
6.01
6.58
6.91
7.49
43
4.62
5.00
5.44
5.69
6.09
Power input (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
1.60
1.63
1.66
1.68
1.70
27
1.84
1.86
1.90
1.92
1.95
30
1.90
1.93
1.97
2.00
2.02
35
2.13
2.16
2.20
2.23
2.26
40
2.30
2.34
2.38
2.41
2.44
43
2.09
2.09
2.09
2.09
2.09
EER
LWT (°C)
7
10
13
15
18
TO
(°C)
20
4.60
4.95
5.32
5.51
5.91
27
3.68
3.97
4.26
4.41
4.73
30
3.39
3.65
3.92
4.07
4.36
35
2.82
3.04
3.26
3.38
3.62
40
2.39
2.57
2.76
2.86
3.07
43
2.21
2.40
2.60
2.72
2.91
TO
:
Outdoor temperature (DB°C)
LWT
:
Leaving water temperature (°C)
Summary of Contents for ESTIA HWS-1102H-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 10: ...9 3 SYSTEM SPECIFICATION ...
Page 12: ...11 4 HYDRO UNIT ...
Page 44: ...43 5 OUTDOOR UNIT ...
Page 57: ...56 6 HOT WATER CYLINDER ...
Page 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 131: ...129 9 OWNER S MANUAL ...
Page 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...